IPI
Command | ASCII (Telnet) | URL Encoded (Web) | Response | Additional |
| (host to intercom) | (host to intercom) | (intercom to host) | description |
|
|
|
|
|
Relay functions |
|
|
|
|
100 Series, IPI 200 Series
Force relay on | 1*1O | 1 %2A1 O | Rly 1 *1 |
Force relay off | 1*0O | 1 %2A0 O | Rly 1 *0] |
Toggle relay | 1*2O | 1%2A2O | Rly 1* X%] |
Pulse relay | 1*3*X6# O | 1%2A3%2AX6# O | Rly 1 * X%] |
|
|
| Rly 1 * X%] |
Turn relay on. Turn relay off.
Toggle relay on/off. X% = 1 (on) or 0 (off).
Set relay’s pulse time (X6#) in 20 ms increments from 1 (20 ms, minimum) to 65535 (1310700 ms, maximum).
Default pulse length is 25 = 500 ms.
• Programming and Control
NIf the verbose mode is enabled, there are two responses from the unit because the relay is pulsed. During a pulse, the relay is toggled to its opposite state and then back to the original state.
View the relay | 1O | 1O |
state |
|
|
Front panel security lockout modes (executive modes)
Off24 | 0X | 0X | Exe 0] |
|
Disable lockout | 1X | 1X | Exe 1] |
|
mode24 |
|
|
|
|
View the lockout | X | X | X20(] |
|
mode status |
|
|
|
|
Example: | X | X | 0] | Executive mode is off. |