Basic Connection and Start-Up
3EPO Port Connection
This optional feature is only for those applications that require connection to a facility’s Emergency Power Off (EPO) circuit. When the UPS is connected to this circuit, it enables emergency shutdown of the UPS’s inverter and inhibits transfer to internal bypass. Using the cable provided, connect the EPO port of your UPS (see 3a ) to a
Note:
1.If using a cable other than what is supplied, the cable should not exceed 350 feet or have a resistance of greater than 10 ohms.
2.If a
CAUTION: The EPO port is not a phone line surge suppressor; do not connect a phone line to this port.
UPS Unit State when asserting EPO with AC line present:
Output | Fans | Serial | SNMP | USB | LCD Screen* |
|
|
|
|
|
|
OFF | ON | ON | ON | ON | sdo |
|
|
|
|
|
|
To restart the UPS unit after asserting EPO with AC line present:
Option 1:
1.Verify that the EPO assertion has been removed or cleared.
2.Press ON button until unit beeps, then release.
3.UPS output will turn back on after it completes diagnostics.
Option 2:
1.Verify that the EPO assertion has been removed or cleared.
2.Remove AC line power to the UPS unit, wait until the LCD is completely off.
3.Reapply AC line power. Now the UPS will start back up in normal operation mode.
UPS Unit State when asserting EPO without AC line power:
Output | Fans | Serial | SNMP | USB | LCD Screen* |
|
|
|
|
|
|
OFF | OFF | OFF | OFF | OFF | sdo |
|
|
|
|
|
|
To restart the UPS unit after asserting EPO without AC line present:
1.Verify that the EPO assertion has been removed or cleared.
2.Reapply AC line power to the UPS unit. Now the UPS will start back up in normal operation mode.
*”sdo” indicates emergency power off
Your model may differ.