Tripp Lite SU1500XLCD, SU1000XLCD, SU2200XLCD External Battery Type selection screen will appear

Page 24

Operation

8The EXTERNAL BATTERY TYPE selection screen will appear.

EXTERNAL BATTERY TYPE refers to the ability for the UPS to become aware of which external battery pack is connected to the UPS. Setting the external battery configuration enhances the accuracy of the MINUTES RUNTIME countdown during power failure conditions. The LCD interface supports no external batteries with the factory configuration of BP0. Two additonal LCD configurable external battery pack options are available under the user selection of BP0, BP1 & BP2. See the table to determine whether BP1 or BP2 applies to your external battery pack. If your battery pack is not listed or you are using more than one of any supported external battery pack, you must use Tripp Lite’s EXTERNAL BATTERY CONFIGURATION TOOL software available for download at this link: http://www.tripplite.com/bpconfig

NOTE: Use the BP0 setting if you plan to use the EXTERNAL BATTERY CONFIGURATION TOOL software. After the software configuration is run, the UPS LCD screen will report “BPC”. The UPS can be reset from BPC to BP0, BP1 or BP2 settings via the LCD screen, but once the new configuration is set, you’ll need to run EXTERNAL BATTERY CONFIGURATION TOOL software again to re-configure back to the unique BPC setting.

UPS MODEL

BP0

BP1

BP2

ALL OTHER BATTERY PACK CONFIGURATIONS

 

 

 

 

 

SU1000XLCD

No BP

Qty 1 BP24V15RT2U

Qty 1 BP24V28-2U

Use EXTERNAL BATTERY CONFIGURATION TOOL software

 

 

 

 

 

SU1500XLCD

No BP

Qty 1 BP48V24-2U

Qty 1 BP48V60RT3U

Use EXTERNAL BATTERY CONFIGURATION TOOL software

 

 

 

 

 

SU2200XLCD

No BP

Qty 1 BP48V24-2U

Qty 1 BP48V60RT3U

Use EXTERNAL BATTERY CONFIGURATION TOOL software

 

 

 

 

 

SU3000XLCD

No BP

Qty 1 BP72V15-2U

Qty 1 BP72V28RT3U

Use EXTERNAL BATTERY CONFIGURATION TOOL software

 

 

 

 

 

ACCEPT AND ADVANCE

VIEW ALTERNATE SETTINGS

LEAVE UPS SETUP MODE

To ACCEPT the current value

&ADVANCE to the next configuration screen, press the ON/SELECT button (less than 1 second).

To VIEW ALTERNATE SETTINGS, press the SETUP BUTTON repeatedly (under 1 second each).

AVAILABLE VALUES

BP0 (factory), BP1, BP2 (BPC reflects a software set configuration)

To leave UPS setup mode, PRESS and HOLD the SETUP BUTTON (about 3 seconds).

9The VIEW IP ADDRESS selection screen will appear.

The VIEW IP ADDRESS is a display field that enables viewing of the current UPS IP address when the SNMPWEBCARD option is in use. The UPS is only capable of displaying a IPv4 level IP address when configured with the SNMPWEBCARD. If VIEW IP ADDRESS is attempted for IPv6 level IP address or for a UPS configuration without the SNMPWEBCARD, the LCD screen will report NA.

ACCEPT AND ADVANCE

VIEW ALTERNATE SETTINGS

LEAVE UPS SETUP MODE

To ADVANCE to back to the OUTPUT VOLTAGE selection screen, press the ON/SELECT button (less than 1 second).

To VIEW IP address information in 3 digit segments, press the SETUP button repeatedly (less than 1 second).

To leave UPS setup mode, PRESS and HOLD the SETUP BUTTON (about 3 seconds).

24

13-03-138 93-3168-EN.indd 24

3/28/2013 1:05:44 PM

Image 24
Contents SmartOnline Parts List Additional Accessories All Models OptionalModel Specific Accessories Optional OverviewImportant Safety Instructions Battery WarningsUPS Location Warnings UPS Connection WarningsFeatures Indicator and Status IconsFront Panel Control Buttons and LCD Screen Label Icons Power on Alarm SilenceCold Start Self TestClear UPS Fault Mode Confirm SelectionTurn OFF UPS Output Enter Setup Mode Advance LCD DisplayRear Panel Features SU2200XLCD SU1500XLCD SU1000XLCD13-03-138 93-3168-EN.indd 28/2013 10504 PM Basic Connection and Start-Up Plug your UPS’s line cord into an electrical outletPlug your equipment into your UPS Online Mode LCD Screen first 20 seconds approx Turn your UPS onOptional Connections Phone Line or Phone/Network Line Surge SuppressionUSB and RS-232 Serial Communications UPS Unit State when asserting EPO with AC line present EPO Port ConnectionExternal Battery Connection On Line Mode On Battery ModeOn Line Mode LCD Viewing Options OperationBypass Mode Standby ModeEconomy Mode Battery Test ModeEconomy Mode LCD Viewing Options SELF-TEST Mode LCD Viewing OptionsFrequency Regulation & Conversion Mode Frequency Regulation / Conversion ModeFrequency Regulation / Conversion Mode UPS Input Test OUT UPS Set-up Using the LCD Screen Accept and Advance View Alternate SettingsOutput Frequency selection screen will appear Frequency Converter selection screen will appearAvailable Values Bypass Range selection screen will appearEconomy Mode selection screen will appear Audible Alarm selection screen will appearOverload Alarm selection screen will appear External Battery Type selection screen will appear View IP Address selection screen will appearVia Snmpwebcard requires firmware version 60 and above Via RS-232 connectionVia USB connection Troubleshooting Internal Battery Replacement+/-DC BUS BUS OVPSU1000XLCD SU1500XLCD and SU2200XLCD SU3000XLCD Model Storage and Service ServiceStorage Warranty Registration 13-03-138 93-3168-EN.indd 28/2013 10608 PM Vita general Lista de Partes Instrucciones Importantes de Seguridad CaracterísticasConexión Básica y Arranque Vista General Lista de PartesAccesorios Adicionales Todos los Modelos Opcionales Accesorio Específicos del Modelo OpcionalInstrucciones Importantes de Seguridad Advertencias de Ubicación del UPSAdvertencias para la Conexión del UPS Advertencias para la Conexión del EquipoCaracterísticas Botones de Control del Panel Frontal y Pantalla LCDIndicador e Iconos de Estado Iconos de Etiquetas Indicadores DE Falla Ícono DE Falla GeneralÍcono DE Falla DE Cableado Ícono DE DerivaciónApagado DE LA Alarma EncendidoArranque EN Frío AUTO-DIAGNÓSTICOConfirme LA Selección Apagado DE Salida DEL UPSBorrado DEL Modo DE Falla DEL UPS DE Falla DEL UPSIngresar a Modo DE Configuración Configuración DEL UPSAvanzar Pantalla LCD Características del Panel Posterior 13-03-138 93-3168-ES.indd 28/2013 10521 PM Conexión Básica y Arranque Enchufe su equipo en su UPSEncienda su UPS Pantalla LCD DE Modo EN Línea primeros 20 segundos aproxConexiones Opcionales Comunicaciones USB y Serial RS-232Conexión del puerto EPO Conexión de la Batería Externa Operación Modos de OperaciónModo EN Línea Modo DE Respaldo POR BateríaModo EN Derivación Modo DE EsperaMuestra DE LA Pantalla LCD EN Modo DE Derivación Modo Económico Modo DE Prueba DE BateríaAUTO-DIAGNÓSTICO Aprobado Modo DE Regulación Y Conversión DE Frecuencia En Modo DE Regulación / Conversión DE FrecuenciaModo DE Regulación / Conversión DE Frecuencia Voltaje Porcentaje DE Carga DE Batería DEL UPSVoltaje DE Batería DEL UPS Configuración del UPS Usando la Pantalla LCD Acepte Y Avance Visualización DE ConfiguracionesAlternas DEL UPS Aparecerá la pantalla de selección de Frecuencia DE Salida Aparecerá la pantalla de selección de Rango DE DerivaciónAparecerá la pantalla de la Alarma Sonora Aparecerá la pantalla de la Alarma DE SobrecargaAparecerá la pantalla de selección de Modo Económico Aparecerá la pantalla de Tipo DE Batería Externa Mediante la conexión RS-232 Mediante la conexión USBSolución de Problemas Reemplazo de Batería InternaBisel para asegurarlo al gabinete SU1500XLCD y SU2200XLCD Modelo SU3000XLCD Almacenamiento y Servicio AlmacenamientoServicio Registro de la garantía 13-03-138 93-3168-ES.indd 28/2013 10608 PM Vue d’ensemble Consignes de sécurité importantes CaractéristiquesConnexion de base et démarrage Accessoires additionnels Tous les modèles optionnel Accessoires spécifiques à certains modèles optionnelVue d’ensemble Liste des piècesRemarque SUR LA Configuration DE LA Batterie Externe Consignes de sécurité importantesBoutons de commande du panneau avant et écran ACL CaractéristiquesIndicateurs et icônes d’état Icônes de message Indicateurs DE Défaillance Icône DE Défaillance GénéraleIcône DE Problème DE Câblage Icône DE DérivationSilence D’ALARME MarcheDémarrage À Froid Test AutomatiqueMode Annuler LA Défaillance DU Système Confirmation DE SélectionÉteindre LA Sortie DU Système ASC Annule LES Modes DE DéfaillanceSE Mettre EN Mode Configuration Entrer LA ConfigurationAvancer L’AFFICHAGE ACL Caractéristiques du panneau arrière 13-03-138 93-3168-FR.indd 28/2013 10543 PM Connexion de base et démarrage Branchez votre matériel dans votre système ASC’ENTRÉE Écran ACL Mode EN Ligne premières 20 secondes approx Mettre votre système ASC Sous TensionConnexions optionnelles Communications en série USB et RS-232Connexion du port EPO Branchement de la batterie externe13-03-138 93-3168-FR.indd 28/2013 10550 PM Lor Mode EN Ligne EN Mode BatterieFonctionnement Modes de fonctionnementMode DE Dérivation Mode DE Veille10 Durée DE Fonctionnement Estimée ’ALIMENTATION DE Sortie EST CoupéeMode Économie Mode Test DE BatterieÉconomie Test Automatique RéussiMode Régulation ET Conversion DE LA Fréquence En Mode RÉGULATION/CONVERSION DE FréquenceÉtat de l’écran ACL et mesures supportées 10e écranConfiguration du système ASC àl’aide de l’écran ACL Quitter LE Mode DE Configuration DU Système ASCAccepter ET Avancer ’écran de sélection de Fréquence DE Sortie apparaîtra ’écran de sélection de Plage DE Dérivation apparaîtra’écran de sélection de Mode Économie apparaîtra ’écran de sélection de l’ALARME Sonore apparaîtra’écran de sélection de l’ALARME DE Surchage apparaîtra ’écran de sélection Type DE Batterie Externe apparaîtra ’écran de sélection Afficher L’ADRESSE IP apparaîtraPar l’intermédiaire de la connexion RS-232 Par l’intermédiaire d’une connexion USBRemplacement de la batterie interne DépannageFixer le panneau sur le boîtier SU1500XLCD et SU2200XLCD Modèle SU3000XLCD Entreposage et entretien EntreposageEntretien Enregistrement de la garantie 13-03-138 933168 Rev D