Internal Battery Replacement
SU3000XLCD Model
1a Remove the screw from the left of the front bezel. 1b Remove the front bezel.
1a
1b
2Remove the screws that hold the metal battery compartment panel in place (in front of the battery compartment on the bottom). Remove the metal panel from the UPS.
2
3Remove the batteries using the pull tab, and disconnect the DC connectors from the UPS.
Note: Please memorize the original battery position and orientation to ensure that you install the new batteries correctly.
4Insert the new battery set into the UPS in the same position as the original set.
5Reconnect the DC connector
6Replace the metal battery compartment panel. Reinstall the screws that hold the metal bar in place.
7Reinstall the front bezel and replace the screw on the left of the bezel to secure it to the cabinet.
3
29
3/28/2013 1:06:07 PM |