Tripp Lite SU2200XLCD, SU1500XLCD Output Frequency selection screen will appear, Available Values

Page 22

Operation

2The OUTPUT FREQUENCY selection screen will appear.

OUTPUT FREQUENCY refers to the cycles-per-second (Hz) of UPS output power. This value is most commonly set to match the prevailing country or region-specific frequency. In general, in the USA, Canada and Mexico use the 60Hz factory setting. In 100-127V 50Hz locations, such as Jamaica, Antigua and parts of Japan, set the UPS to 50Hz. To successfully configure your UPS to convert frequency from 50-to-60Hz or 60-to-50Hz, set BOTH the OUTPUT FREQUENCY to the desired setting and enable this function by setting the FREQ CONVERSION to ENABLE.

ACCEPT AND ADVANCE

VIEW ALTERNATE SETTINGS

LEAVE UPS SETUP MODE

To ACCEPT the current value

&ADVANCE to the next configuration screen, press the ON/SELECT button (less than 1 second).

To VIEW ALTERNATE SETTINGS, press the SETUP BUTTON repeatedly (under 1 second each).

AVAILABLE VALUES 60Hz (factory), 50Hz

To leave UPS setup mode,

PRESS and HOLD the SETUP

BUTTON (about 3 seconds).

NOTE - the UPS must be in STANDBY MODE to change the output frequency setting

3The FREQUENCY CONVERTER selection screen will appear.

FREQUENCY CONVERTER refers to the ability of the UPS to convert 60Hz to 50Hz or 50Hz to 60Hz. The UPS system automatically selects 50 Hz or 60 Hz operation based on utility power conditions at start-up. The factory configuration of OFF is ideal for most applications. Some users may wish to convert frequency for connected equipment. To successfully configure your UPS for frequency conversion, turn ON the FREQUENCY CONVERTER function and SET the OUTPUT FREQUENCY function to the desired 50 or 60 Hz setting.

ACCEPT AND ADVANCE

VIEW ALTERNATE SETTINGS

LEAVE UPS SETUP MODE

To ACCEPT the current value

&ADVANCE to the next configuration screen , press the ON/SELECT button (less than 1 second).

To VIEW ALTERNATE SETTINGS, press the SETUP BUTTON repeatedly (under 1 second each).

AVAILABLE VALUES

OFF(factory), ON

To leave UPS setup mode,

PRESS and HOLD the SETUP

BUTTON (about 3 seconds).

NOTE - the UPS must be in STANDBY MODE to change the frequency converter setting

4The BYPASS RANGE selection screen will appear.

BYPASS RANGE: Sets the allowable voltage deviation from nominal input voltage that is acceptable for the unit to go to bypass in a fault condition. If the voltage goes outside the range, the unit will not go to bypass. If the unit is already in bypass, it will turn the output off. The factory setting of WIDE is compatible with the vast majority of networking equipment. Regardless of the “plus or minus” value entered, the highest bypass voltage available is 135V. The lowest bypass voltage available is 90V (full load) and 70V (<70% load). The “Wide” range reflects these same values (full load 90 to 135V / <70% load 70 to 135V).

ACCEPT AND ADVANCE

VIEW ALTERNATE SETTINGS

LEAVE UPS SETUP MODE

To ACCEPT the current value

&ADVANCE to the next configuration screen, press the ON/SELECT button (less than 1 second).

To VIEW ALTERNATE SETTINGS, press the SETUP BUTTON repeatedly (under 1 second each).

AVAILABLE VALUES

HI (factory), 5%, 6%, 7%, 8%, 9%, 10%, 11%, 12%, 13%, 14%, 15%

22

To leave UPS setup mode, PRESS and HOLD the SETUP BUTTON (about 3 seconds).

13-03-138 93-3168-EN.indd 22

3/28/2013 1:05:38 PM

Image 22
Contents SmartOnline Model Specific Accessories Optional Parts ListAdditional Accessories All Models Optional OverviewUPS Location Warnings Important Safety InstructionsBattery Warnings UPS Connection WarningsIndicator and Status Icons FeaturesFront Panel Control Buttons and LCD Screen Label Icons Cold Start Power onAlarm Silence Self TestConfirm Selection Clear UPS Fault ModeTurn OFF UPS Output Enter Setup Mode Advance LCD DisplayRear Panel Features SU2200XLCD SU1500XLCD SU1000XLCD13-03-138 93-3168-EN.indd 28/2013 10504 PM Plug your UPS’s line cord into an electrical outlet Basic Connection and Start-UpPlug your equipment into your UPS Online Mode LCD Screen first 20 seconds approx Turn your UPS onPhone Line or Phone/Network Line Surge Suppression Optional ConnectionsUSB and RS-232 Serial Communications UPS Unit State when asserting EPO with AC line present EPO Port ConnectionExternal Battery Connection On Line Mode LCD Viewing Options On Line ModeOn Battery Mode OperationBypass Mode Standby ModeEconomy Mode LCD Viewing Options Economy ModeBattery Test Mode SELF-TEST Mode LCD Viewing OptionsFrequency Regulation / Conversion Mode Frequency Regulation & Conversion ModeFrequency Regulation / Conversion Mode UPS Input Test OUT UPS Set-up Using the LCD Screen Accept and Advance View Alternate SettingsAvailable Values Output Frequency selection screen will appearFrequency Converter selection screen will appear Bypass Range selection screen will appearAudible Alarm selection screen will appear Economy Mode selection screen will appearOverload Alarm selection screen will appear External Battery Type selection screen will appear View IP Address selection screen will appearVia RS-232 connection Via Snmpwebcard requires firmware version 60 and aboveVia USB connection +/-DC BUS TroubleshootingInternal Battery Replacement BUS OVPSU1000XLCD SU1500XLCD and SU2200XLCD SU3000XLCD Model Service Storage and ServiceStorage Warranty Registration 13-03-138 93-3168-EN.indd 28/2013 10608 PM Instrucciones Importantes de Seguridad Características Vita general Lista de PartesConexión Básica y Arranque Accesorios Adicionales Todos los Modelos Opcionales Vista GeneralLista de Partes Accesorio Específicos del Modelo OpcionalAdvertencias para la Conexión del UPS Instrucciones Importantes de SeguridadAdvertencias de Ubicación del UPS Advertencias para la Conexión del EquipoBotones de Control del Panel Frontal y Pantalla LCD CaracterísticasIndicador e Iconos de Estado Ícono DE Falla DE Cableado Iconos de EtiquetasIndicadores DE Falla Ícono DE Falla General Ícono DE DerivaciónArranque EN Frío Apagado DE LA AlarmaEncendido AUTO-DIAGNÓSTICOBorrado DEL Modo DE Falla DEL UPS Confirme LA SelecciónApagado DE Salida DEL UPS DE Falla DEL UPSConfiguración DEL UPS Ingresar a Modo DE ConfiguraciónAvanzar Pantalla LCD Características del Panel Posterior 13-03-138 93-3168-ES.indd 28/2013 10521 PM Conexión Básica y Arranque Enchufe su equipo en su UPSEncienda su UPS Pantalla LCD DE Modo EN Línea primeros 20 segundos aproxConexiones Opcionales Comunicaciones USB y Serial RS-232Conexión del puerto EPO Conexión de la Batería Externa Modo EN Línea OperaciónModos de Operación Modo DE Respaldo POR BateríaModo DE Espera Modo EN DerivaciónMuestra DE LA Pantalla LCD EN Modo DE Derivación Modo DE Prueba DE Batería Modo EconómicoAUTO-DIAGNÓSTICO Aprobado En Modo DE Regulación / Conversión DE Frecuencia Modo DE Regulación Y Conversión DE FrecuenciaModo DE Regulación / Conversión DE Frecuencia Porcentaje DE Carga DE Batería DEL UPS VoltajeVoltaje DE Batería DEL UPS Acepte Y Avance Visualización DE Configuraciones Configuración del UPS Usando la Pantalla LCDAlternas DEL UPS Aparecerá la pantalla de selección de Frecuencia DE Salida Aparecerá la pantalla de selección de Rango DE DerivaciónAparecerá la pantalla de la Alarma DE Sobrecarga Aparecerá la pantalla de la Alarma SonoraAparecerá la pantalla de selección de Modo Económico Aparecerá la pantalla de Tipo DE Batería Externa Mediante la conexión RS-232 Mediante la conexión USBSolución de Problemas Reemplazo de Batería InternaBisel para asegurarlo al gabinete SU1500XLCD y SU2200XLCD Modelo SU3000XLCD Almacenamiento Almacenamiento y ServicioServicio Registro de la garantía 13-03-138 93-3168-ES.indd 28/2013 10608 PM Consignes de sécurité importantes Caractéristiques Vue d’ensembleConnexion de base et démarrage Vue d’ensemble Accessoires additionnels Tous les modèles optionnelAccessoires spécifiques à certains modèles optionnel Liste des piècesRemarque SUR LA Configuration DE LA Batterie Externe Consignes de sécurité importantesCaractéristiques Boutons de commande du panneau avant et écran ACLIndicateurs et icônes d’état Icône DE Problème DE Câblage Icônes de messageIndicateurs DE Défaillance Icône DE Défaillance Générale Icône DE DérivationDémarrage À Froid Silence D’ALARMEMarche Test AutomatiqueÉteindre LA Sortie DU Système ASC Mode Annuler LA Défaillance DU SystèmeConfirmation DE Sélection Annule LES Modes DE DéfaillanceEntrer LA Configuration SE Mettre EN Mode ConfigurationAvancer L’AFFICHAGE ACL Caractéristiques du panneau arrière 13-03-138 93-3168-FR.indd 28/2013 10543 PM Branchez votre matériel dans votre système ASC Connexion de base et démarrage’ENTRÉE Écran ACL Mode EN Ligne premières 20 secondes approx Mettre votre système ASC Sous TensionConnexions optionnelles Communications en série USB et RS-232Connexion du port EPO Branchement de la batterie externe13-03-138 93-3168-FR.indd 28/2013 10550 PM Fonctionnement Lor Mode EN LigneEN Mode Batterie Modes de fonctionnement10 Durée DE Fonctionnement Estimée Mode DE DérivationMode DE Veille ’ALIMENTATION DE Sortie EST CoupéeÉconomie Mode ÉconomieMode Test DE Batterie Test Automatique RéussiMode Régulation ET Conversion DE LA Fréquence En Mode RÉGULATION/CONVERSION DE FréquenceÉtat de l’écran ACL et mesures supportées 10e écranQuitter LE Mode DE Configuration DU Système ASC Configuration du système ASC àl’aide de l’écran ACLAccepter ET Avancer ’écran de sélection de Fréquence DE Sortie apparaîtra ’écran de sélection de Plage DE Dérivation apparaîtra’écran de sélection de l’ALARME Sonore apparaîtra ’écran de sélection de Mode Économie apparaîtra’écran de sélection de l’ALARME DE Surchage apparaîtra ’écran de sélection Type DE Batterie Externe apparaîtra ’écran de sélection Afficher L’ADRESSE IP apparaîtraPar l’intermédiaire de la connexion RS-232 Par l’intermédiaire d’une connexion USBRemplacement de la batterie interne DépannageFixer le panneau sur le boîtier SU1500XLCD et SU2200XLCD Modèle SU3000XLCD Entreposage Entreposage et entretienEntretien Enregistrement de la garantie 13-03-138 933168 Rev D