Operation (Special Conditions) (continued)
OPERATION OF MANUAL BYPASS SWITCH
Turn this switch to “BYPASS” before performing any maintenance on the UPS with the connected load supported. Connected equipment will receive filtered AC mains power, but will not receive battery power in the event of a blackout.
SWITCHING UPS TO “BYPASS” MODE
•Press the “OFF” button.
•Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.
•Turn the Main Input Switch Circuit Breaker OFF.
SWITCHING UPS TO “NORMAL” MODE
•Turn the Main Input Switch Circuit Breaker ON.
•Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.
•Press the “ON” button.
Communications
RS-232 INTERFACE
This female DB9 port connects your UPS via an
Hardware: |
| Pin assignment: | |
Baud Rate: | 2400 BPS | Pin 2: TXD (Transmit Data) | |
Data Length: | 8 bits | Pin 3: | RXD (Receive Data) |
Stop Bit: | 1 bit | Pin 5: | GND (Signal Ground) |
Parity: | NONE |
|
|
AS-400 INTERFACE
This female DB9 port connects your UPS to an IBM
computer via an
Pin assignment:
Pin 5: | Common |
Pin 6: | Operation on AC power supply |
Pin 7: | Low battery alarm |
Pin 8: | Operation on inverter |
Pin 9: | Operation on battery |
AS-400 INTERFACE TABLE
| Pin 6,5 | Pin 7,5 | Pin 8,5 | Pin 9,5 |
|
|
|
|
|
Battery | OFF | * | ON | ON |
Low Battery | OFF | ON | ON | ON |
|
|
|
|
|
Direct Mains Supply | ON | OFF | OFF | OFF |
|
|
|
|
|
Inverter | OFF | * | ON | * |
|
|
|
|
|
* Inactive: may be in either state.