Tripp Lite Power Supply UPS Location, Mounting Bracket Installation, Grounding Connection

Page 6

Installation

UPS LOCATION

Move your UPS over short distances using its wheels. NOTE: the wheels are not designed to provide long-term support for the UPS system after final installation. Mounting bracket installation is required.

MOUNTING BRACKET INSTALLATION

DANGER!

RISK OF PRODUCT DAMAGE AND SERIOUS PERSONAL INJURY

The UPS System's wheels are not designed to provide long-term support for the UPS system after final installation. MOUNTING BRACKET INSTALLATION IS REQUIRED. If the mounting brackets are not installed, the wheels may eventually fail and potentially damage the UPS System and cause serious personal injury.

Using the included bolts, install one mounting bracket on each side of the UPS System as shown. If desired, install the bracket to the floor surface with user-supplied hardware.

Front View

GROUNDING CONNECTION

Using a user-supplied 4 AWG ground wire, connect the UPS System's ground lug to earth ground. Tighten connections with a torque of not less than 35 inch-lbs. (3.9 NM). Keep ground wire connected at all times after installation.

Rear View

UPS INPUT AND OUTPUT HARDWIRE CONNECTION

In addition to the instructions listed below, follow all warnings found in the Safety section prior to connection.

Install with flex cable of sufficient length to move UPS clear of surrounding equipment for servicing (sides and rear).

Use ferrule caps to cover termination cables connected to UPS to avoid frayed ends from shorting on terminal block.

Neutral conductor must be same size as current conductors.

WIRING SELECTION

Choose appropriate cabling (rated VW-1, FT-1 or better) to connect your UPS to an AC power supply and your equipment.

UPS System Model

Wiring Size

20kVA

6 AWG / 14 mm2

30kVA

4 AWG / 22 mm2

Maximum Cable Length: 10 m (32.8 ft)

6

Image 6
Contents Español Français Important Safety Warnings UPS Location WarningsFront Panel Control PanelBattery Access Panel cover removed Rear Panel Rear PanelUPS Input and Output Hardwire Connection InstallationMounting Bracket Installation UPS LocationOperation Normal Conditions Initial Battery ChargingWiring Connection Output Voltage Selection VIA SoftwareTurning the UPS OFF SELF-TESTINGSelf Testing Battery OK DC to DC OK Inverter Test LCD Display Select ButtonInverter on Warnings Operation Special ConditionsOperation on BYPASS-VOLTAGE OUT of Range Operation Under ShutdownCommunications DRY Contact Interface Table Remote Emergency Power OFF EPODRY Contact Interface OpenCheck Battery Pack Voltage Before Completing Installation Do not Remove Battery SleeveBattery Packs are Heavy Adding or Replacing Internal BatteriesInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Adding or Replacing Internal Batteries Adding or Replacing Internal Batteries Limited Warranty ServiceWarranty Observe Proper PolaritySpecifications Model SU20K3/3INTModel SU30K3/3INT Manual del Propietario Advertencias de Seguridad Importantes Advertencias sobre la colocación y ubicación del UPSPanel Frontal Panel DE ControlPanel Frontal continuación Panel DE Acceso a LA Bateria Tapa RemovidaPanel Trasero Panel TraseroInstalacion DE LOS Soportes DE Montaje InstalaciónUbicación DEL UPS Conexion a TierraSeleccion DEL Voltaje DE Salida VIA Software Operación Condiciones NormalesCarga Inicial DE LA Bateria Encendiendo EL UPSAUTO-PRUEBA Operación Condiciones Normales continuaciónApagando EL UPS Boton Select Seleccionar DE LA Pantalla LCDAdvertencias DEL Inversor Encendido Operación Condiciones EspecialesOperacion EN DERIVACION-VOLTAJE Fuera DE Rango Operacion Bajo CIERRE/PARADAOperación Condiciones Especiales continuación ComunicacionesApagado DE Emergencia Remoto EPO Comunicaciones continuaciónInterfaz DEL Contacto Seco Tabla DE LA Interfaz DE Contacto SecoAñadiendo o Remplazando las Baterías Internas ¡NO Remueva LA Cubierta Protectora DE LA Bateria¡LOS Modulos DE Bateria SON Pesados Diagrama DEL Cableado DEL Modulo DE Baterias Internas Añadiendo o Remplazando las Baterías Internas continuaciónAñadiendo o Remplazando las Baterías Internas continuación Terminales ¡PELIGRO Garantia Limitada ServicioGarantía ¡OBSERVE LA Polaridad CorrectaEspecificaciones Modelo SU20K3/3INTEspecificaciones continuación Modelo SU30K3/3INTManuel du propriétaire Importantes consignes de sécurité Mises en garde relatives à la localisation de londuleurPanneau DE Commande Panneau avantPanneau avant suite Panneau Daccès AUX Batteries carter enlevéPanneau arrière Panneau ArrièreConnexion DE Mise À LA Terre IL Faut Installer Londuleur À Laide DE Brides DE FixationMises EN Garde Relatives À LA Localisation DE Londuleur Sélection DU CâblagePremière Charge DE LA Batterie Installation suiteFonctionnement Conditions normales Sélection DE LA Tension DE Sortie À Laide DUN LogicielÉxécution DUN AUTO-TEST Fonctionnement Conditions normales suiteArrêter Londuleur Bouton DE Sélection DE Lécran ACLMises EN Garde Inverseur EN Marche Fonctionnement Conditions spécialesFonctionnement EN DÉRIVATION-TENSION Hors Plag Fonctionnement Pendant UN ArrêtFonctionnement DU Commutateur DE Dérivation Manuelle Commuter Londuleur EN Mode NormalFonctionnement Conditions spéciales suite Interface RS-232Communications suite Ajout et remplacement des batteries internesArrêt Durgence Emergency Power OFF EPO À Distance Interface Contact SECAjout et remplacement des batteries internes suite Schéma DU Câblage Interne DUN Bloc DE BatterieAjout et remplacement des batteries internes suite Bornes Ajout et remplacement des batteries internes suite Garantie Garantie Limitée À VIEObserver LA Bonne Polarité Spécifications Modèle SU20K3/3INTSpécifications suite Modèle SU30K3/3INT