Paradyne 3611, 3610, 3600 Series Features, 2illustrates the CO Power Unit with two power modules

Page 12

COMSPHERE ±48 Vdc Central Office Power Unit

NOTE

Customer-supplied cable assemblies must comply with items 5 and 6 of the Important Safety Instructions at the front of this guide.

For more information on the alarm cables and NMS adapter cable, see Appendix A of this guide.

Part numbers for the CO Power Unit and its related components are listed in Appendix B of this guide.

Features

The CO Power Unit provides the following features:

Enables DCEs supported by the COMSPHERE 3000 Series Carrier to operate in a ± 48 Vdc central office environment.

Provides the following three modes of operation:

ÐBasic mode ± the mode in which the single power module supplies power to the entire carrier. This mode of operation is the only mode available for the CO Power Unit with one power module.

ÐRedundant mode ± the mode in which two power modules supply power to the entire carrier. If one power module fails, the remaining power module assumes the full load of the carrier. To operate in this mode of operation, you must install an optional second power module in the CO Power Unit.

ÐIndependent mode ± the mode in which each of the two power modules supplies power to one-half of the carrier. To operate in this mode of operation, you must install an optional second power module in the CO Power Unit.

Provides forced air cooling for the carrier via a

± 48 Vdc fan in the power module.

Provides an optional air filter which prevents dust from entering the CO Power Unit and the COMSPHERE 3000 Series Carrier.

Detects power module and fan failures by monitoring the power output levels and the fan's low-speed sensor for proper operation of the power module. When a failure occurs, an alarm indication light appears on the power module's faceplate.

Sends power failure and/or fan failure alarms to a CO alarm system and/or a 6800 Series NMS via a Modular 3611 DSU.

Figure 1-1illustrates the CO Power Unit with one power module in the left side of the CO power tray. In Basic mode, the single power module can be installed in either the left or right side of the CO power tray.

Figure 1-2illustrates the CO Power Unit with two power modules.

1-2

May 1998

3000-A2-GB41-40

Image 12
Contents Comsphere ±48 Vdc Central Office Power Unit Warranty, Sales, and Service Information TrademarksCopyright  1998 Paradyne Corporation. All rights reserved Important Safety Instructions Comsphere ±48 Vdc Central Office Power Unit Table of Contents Interface Connections Glossary Index List of Figures Technical Specifications for Central Office CO Power Unit List of TablesPreface Objectives and Reader AssumptionsAbstract Related DocumentsComsphere ±48 Vdc Central Office Power Unit Introduction OverviewFeatures 2illustrates the CO Power Unit with two power modulesCentral Office CO Power Unit with One Power Module Technical Specifications ±48 VdcEquipment Warranty Support WeightComsphere ±48 Vdc Central Office Power Unit May Installation Considerations Basic Mode of OperationIndependent Mode of Operation Ambient 3611 DSUs 3551, 3611,3161 DSU/CSUs Without DBMs DSUs with DBMs DSUs, 3151 and CSUsRedundant Mode of Operation Alarm Forwarding to a 6800 Series NMSCO Power Unit Installation Installing the Optional Second Power ModuleProcedure Installing the Optional Second Power Module Setting the Option Straps Settings for Basic ModeIndependent Mode Settings for Independent ModeInstalling the CO Power Unit Series Carrier Installation ManualCO Power Unit Installation Providing Power to a CO Power Unit Comsphere 3000 Series Carrier RearAMP Procedure GRD Optional Fuses -48V GRD Vdc Power Source a Installing an Sdcp  ProcedureConnecting the Alarm Contacts to a CO Alarm System Ext Leads RPowr Procedure Installation Air Filter and Brackets Installation Optional 11. Air Filter Brackets Installation Comsphere ±48 Vdc Central Office Power Unit May Troubleshooting and Maintenance Indicators and ControlsTroubleshooting Power Module Replacement Instructions Replacing a Power ModulePreventive Maintenance Interface Connections a DC Inputs±48V CO ground return Figure A-2. Connector Housing and Contact CO Alarm System Outputs CO Alarm System OutputsTable A-3 Pin Assignments forNMS Alarm Outputs Figure A-3. NMS Adapter Cable Feature Number 3000-F2-510 Basic mode GlossarySDU Index NMS Index