Paradyne 3610, 3611, 3600 Series manual Setting the Option Straps, Settings for Basic Mode

Page 22

COMSPHERE ±48 Vdc Central Office Power Unit

Setting the Option Straps

The option straps are screw switches that are set by raising (loosening) or lowering (tightening) the screw to break or make the contact. There are five option straps, S1 through S5, on the CO Power Unit's backplane (see Figure 2-2).

NOTE

Older power modules have straps labeled S1 and S2. These should always be in the raised position.

Basic Mode

If you want to operate in the Basic mode, you must use one ± 48 Vdc power source and configure the option straps as shown in Table 2-2.

Table 2-2

Settings for Basic Mode

S1 Lowered

S2 Lowered

S3 Lowered

S4 Lowered

S5 Lowered

To set the option straps for Basic mode of operation:

"Procedure

1.Tighten the screws on all five straps (S1 through S5) on the CO Power Unit's backplane. Make sure that the screws are securely touching the contacts, but do not screw the straps too tight because doing so can damage the equipment.

CO Power Tray

S1

S3

CO Power Unit

Backplane

S5 S2

S4

496-13695-01

Figure 2-2. Option Straps (S1 through S5) on the CO Power Unit's Backplane

2-6

May 1998

3000-A2-GB41-40

Image 22
Contents Comsphere ±48 Vdc Central Office Power Unit Trademarks Warranty, Sales, and Service InformationCopyright  1998 Paradyne Corporation. All rights reserved Important Safety Instructions Comsphere ±48 Vdc Central Office Power Unit Table of Contents Interface Connections Glossary Index List of Figures Technical Specifications for Central Office CO Power Unit List of TablesAbstract PrefaceObjectives and Reader Assumptions Related DocumentsComsphere ±48 Vdc Central Office Power Unit Introduction OverviewFeatures 2illustrates the CO Power Unit with two power modulesCentral Office CO Power Unit with One Power Module Technical Specifications ±48 VdcEquipment Warranty Support WeightComsphere ±48 Vdc Central Office Power Unit May Installation Considerations Basic Mode of Operation3161 DSU/CSUs Independent Mode of OperationAmbient 3611 DSUs 3551, 3611, Without DBMs DSUs with DBMs DSUs, 3151 and CSUsRedundant Mode of Operation Alarm Forwarding to a 6800 Series NMSInstalling the Optional Second Power Module CO Power Unit InstallationProcedure Installing the Optional Second Power Module Setting the Option Straps Settings for Basic ModeIndependent Mode Settings for Independent ModeInstalling the CO Power Unit Series Carrier Installation ManualCO Power Unit Installation Providing Power to a CO Power Unit Comsphere 3000 Series Carrier RearAMP Procedure GRD Optional Fuses -48V GRD Vdc Power Source a Installing an Sdcp  ProcedureConnecting the Alarm Contacts to a CO Alarm System Ext Leads RPowr Procedure Installation Air Filter and Brackets Installation Optional 11. Air Filter Brackets Installation Comsphere ±48 Vdc Central Office Power Unit May Troubleshooting and Maintenance Indicators and ControlsTroubleshooting Power Module Replacement Instructions Replacing a Power ModulePreventive Maintenance Interface Connections a DC Inputs±48V CO ground return Figure A-2. Connector Housing and Contact Table A-3 CO Alarm System OutputsCO Alarm System Outputs Pin Assignments forNMS Alarm Outputs Figure A-3. NMS Adapter Cable Feature Number 3000-F2-510 Basic mode GlossarySDU Index NMS Index