Paradyne 3610 manual Independent Mode of Operation, Ambient 3611 DSUs 3551, 3611, 3161 DSU/CSUs

Page 18

COMSPHERE ±48 Vdc Central Office Power Unit

directly above the bottom carrier should have its power module installed in the right side of its CO power tray. Then, the next carrier directly above should have its power module installed in the left side of its CO power tray, and so on for the remainder of the carriers in the cabinet. For information on removing and installing a power module, see the Power Module Replacement Instructions section in Chapter 3.

With the power modules placed in alternating sequence, the maximum operating ambient temperatures listed in Table 2-1are permitted.

Independent Mode of Operation

In the Independent mode of operation, the left power module (as viewed from the front of the carrier) powers Slots 1 through 8 of the carrier and the right power module powers Slots 9 through 16 of the carrier. The Shared Diagnostic Unit (SDU), contained in Slot 0, is powered by both power modules. If a power module fails, only the service to that side of the carrier is disrupted. The other side of the carrier is unaffected. Do not remove a

failed power module until a replacement is available. To replace a power module, see the Power Module Replacement Instructions section in Chapter 3 of this guide.

When the power modules are configured for Independent mode of operation, up to six carriers can be mounted in a cabinet. The maximum ambient temperature is 50°C.

The ± 48 Vdc input can be provided in one of two powering options:

Using two separate ± 48 Vdc power sources and two input power cables.

Using one ± 48 Vdc power source and two input power cables.

For maximum reliability, use the first option. For more information on these powering options, see the Providing Power to a CO Power Unit section.

To change the mode of operation, see the Setting the Option Straps section.

Table 2-1

Maximum Ambient Temperatures Permitted

 

 

Allowable Number of Stacked COMSPHERE 3000 Series

 

Maximum

 

Carriers in a Cabinet

 

 

 

 

 

 

Ambient

3551 and 3611 DSUs

3551, 3611, and 3616

 

 

Temperature

3161 DSU/CSUs 1

 

without DBMs, 3511

DSUs with DBMs and

 

 

DSUs, 3151 and CSUs 2

3811 Modems 2

 

 

122°F (50°C)

4

2

See Note 4

 

 

 

 

 

 

113°F (45°C)

5

3

13, 2

 

104°F (40°C)

6

4

3

 

 

 

 

 

 

95°F (35°C)

6

5

4

 

 

 

 

 

 

86°F (30°C)

6

5

5

 

 

 

 

 

 

77°F (25°C)

6

6

6

 

 

 

 

NOTES:

 

 

 

1

These operating ambient temperatures can be increased by 5°C by placing 3161 DSU/CSUs in cooler

 

slots (2, 3, 4, 5, 10, 11, 12, 13), or by leaving a slot empty next to each 3161 DSU/CSU.

2

Use the strictest cooling requirements when there is a mixture of units installed.

 

3

Requires a power module on each side, otherwise the ambient temperature must be restricted to 35°C.

4

A single carrier, equipped with two power modules, can operate at 50°C provided the cooler slots (2, 3, 4,

 

5, 10, 11, 12, 13) are used.

 

 

 

 

 

 

 

2-2

May 1998

3000-A2-GB41-40

Image 18
Contents Comsphere ±48 Vdc Central Office Power Unit Warranty, Sales, and Service Information TrademarksCopyright  1998 Paradyne Corporation. All rights reserved Important Safety Instructions Comsphere ±48 Vdc Central Office Power Unit Table of Contents Interface Connections Glossary Index List of Figures Technical Specifications for Central Office CO Power Unit List of TablesAbstract PrefaceObjectives and Reader Assumptions Related DocumentsComsphere ±48 Vdc Central Office Power Unit Introduction OverviewFeatures 2illustrates the CO Power Unit with two power modulesCentral Office CO Power Unit with One Power Module Technical Specifications ±48 VdcEquipment Warranty Support WeightComsphere ±48 Vdc Central Office Power Unit May Installation Considerations Basic Mode of Operation3161 DSU/CSUs Independent Mode of OperationAmbient 3611 DSUs 3551, 3611, Without DBMs DSUs with DBMs DSUs, 3151 and CSUsRedundant Mode of Operation Alarm Forwarding to a 6800 Series NMSCO Power Unit Installation Installing the Optional Second Power ModuleProcedure Installing the Optional Second Power Module Setting the Option Straps Settings for Basic ModeIndependent Mode Settings for Independent ModeInstalling the CO Power Unit Series Carrier Installation ManualCO Power Unit Installation Providing Power to a CO Power Unit Comsphere 3000 Series Carrier RearAMP Procedure GRD Optional Fuses -48V GRD Vdc Power Source a Installing an Sdcp  ProcedureConnecting the Alarm Contacts to a CO Alarm System Ext Leads RPowr Procedure Installation Air Filter and Brackets Installation Optional 11. Air Filter Brackets Installation Comsphere ±48 Vdc Central Office Power Unit May Troubleshooting and Maintenance Indicators and ControlsTroubleshooting Power Module Replacement Instructions Replacing a Power ModulePreventive Maintenance Interface Connections a DC Inputs±48V CO ground return Figure A-2. Connector Housing and Contact Table A-3 CO Alarm System OutputsCO Alarm System Outputs Pin Assignments forNMS Alarm Outputs Figure A-3. NMS Adapter Cable Feature Number 3000-F2-510 Basic mode GlossarySDU Index NMS Index