Page 23

Installation

Independent Mode

If you want to operate in Independent mode and you plan to use either one or two ± 48 Vdc power sources, configure the option straps as shown in Table 2-3.

Table 2-3

Settings for Independent Mode

S1 Raised

S2 Raised

S3 Raised

S4 Raised

S5 Raised

To set the option straps for Independent mode of operation:

"Procedure

1.Loosen the screws on all five straps (S1 through S5) on the CO Power Unit's backplane so that the screws are not touching the contacts. (Two complete turns will suffice.)

Redundant Mode Ð One Source, One Cable

If you want to operate in Redundant mode and you plan to use a single ± 48 Vdc power source and a single input power cable, configure the option straps as shown in Table 2-4.

Table 2-4

Settings for Redundant Mode

Using a Single ±48 Vdc Power Source and a Single Input Power Cable

S1 Lowered

S2 Lowered

S3 Lowered

S4 Lowered

S5 Lowered

To set the option straps for Redundant mode of

operation using a single ± 48 Vdc power source and a single input power cable:

"Procedure

1.Tighten the screws on all five straps (S1 through S5) on the CO Power Unit's backplane. Make sure

that the screws are securely touching the contacts, but do not screw the straps too tight because doing so can damage the equipment.

Redundant Mode Ð Two Cables

If you want to operate in Redundant mode and you plan to use either a single ± 48 Vdc power source and two input power cables or two separate ± 48 Vdc power sources and two input power cables, configure the option straps as shown in Table 2-5.

Table 2-5

Settings for Redundant Mode with Either a Single Power Source and Two Input Power Cables, or Two Separate

Power Sources and Two Input Power Cables

S1 Lowered

S2 Lowered

S3 Lowered

S4 Raised

S5 Raised

To set the option straps for Redundant mode of operation with either a single power source and two input power cables, or two separate power sources and two input power cables:

"Procedure

1.Tighten the screws on the S1, S2, and S3 straps on the CO Power Unit's backplane. Do not screw the straps too tight because doing so can damage the equipment. Make sure that the screws are securely touching the contacts. Then loosen the screws on the S4 and S5 straps. (Two complete turns will suffice.)

NOTE

In either Independent or Redundant mode of operation, the S4 and S5 straps on the backplane must be raised (loosened) when two separate ±48 Vdc power sources are used to prevent operational problems and voltage incompatibilities.

3000-A2-GB41-40

May 1998

2-7

Image 23
Contents Comsphere ±48 Vdc Central Office Power Unit Copyright  1998 Paradyne Corporation. All rights reserved Warranty, Sales, and Service InformationTrademarks Important Safety Instructions Comsphere ±48 Vdc Central Office Power Unit Table of Contents Interface Connections Glossary Index List of Figures List of Tables Technical Specifications for Central Office CO Power UnitRelated Documents PrefaceObjectives and Reader Assumptions AbstractComsphere ±48 Vdc Central Office Power Unit Overview Introduction2illustrates the CO Power Unit with two power modules FeaturesCentral Office CO Power Unit with One Power Module ±48 Vdc Technical SpecificationsWeight Equipment Warranty SupportComsphere ±48 Vdc Central Office Power Unit May Basic Mode of Operation Installation ConsiderationsWithout DBMs DSUs with DBMs DSUs, 3151 and CSUs Independent Mode of OperationAmbient 3611 DSUs 3551, 3611, 3161 DSU/CSUsAlarm Forwarding to a 6800 Series NMS Redundant Mode of OperationProcedure CO Power Unit InstallationInstalling the Optional Second Power Module Installing the Optional Second Power Module Settings for Basic Mode Setting the Option StrapsSettings for Independent Mode Independent ModeSeries Carrier Installation Manual Installing the CO Power UnitCO Power Unit Installation Comsphere 3000 Series Carrier Rear Providing Power to a CO Power UnitAMP Procedure GRD Optional Fuses -48V GRD Vdc Power Source a  Procedure Installing an SdcpConnecting the Alarm Contacts to a CO Alarm System Ext Leads RPowr Procedure Installation Air Filter and Brackets Installation Optional 11. Air Filter Brackets Installation Comsphere ±48 Vdc Central Office Power Unit May Indicators and Controls Troubleshooting and MaintenanceTroubleshooting Replacing a Power Module Power Module Replacement InstructionsPreventive Maintenance DC Inputs Interface Connections a±48V CO ground return Figure A-2. Connector Housing and Contact Pin Assignments for CO Alarm System OutputsCO Alarm System Outputs Table A-3NMS Alarm Outputs Figure A-3. NMS Adapter Cable Feature Number 3000-F2-510 Glossary Basic modeSDU Index NMS Index