Paradyne 3600 Series, 3611, 3610 manual Technical Specifications, ±48 Vdc

Page 14

COMSPHERE ±48 Vdc Central Office Power Unit

Technical Specifications

Technical specifications for the CO Power Unit (which includes one power module) are listed in Table 1-1.

Table 1-1

(1 of 2)

Technical Specifications for Central Office (CO) Power Unit

Technical Specifications

Criteria

 

 

ENVIRONMENT

 

Operating Temperature

32°F (0°C) to 122°F (50°C) (See the Installation Considerations

 

section in Chapter 2 for additional operating temperature limits.)

Relative Humidity

5% to 95% (noncondensing)

Storage Temperature

±4°F (±20°C) to 158 5F (70°C)

Shock and Vibration

Withstands normal shipping and handling

 

 

POWER REQUIREMENTS

 

CO Power Unit (with 16 fully equipped

±60 Vdc to ±40 Vdc (4.5 amps maximum)

3611 DSUs in the carrier)

 

CO Power Unit (with 16 fully equipped

±60 Vdc to ±40 Vdc (2.3 amps maximum)

3151 CSUs in the carrier)

 

CO Power Unit (with 16 fully equipped

±60 Vdc to ±40 Vdc (4.8 amps maximum)

3161 DSU/CSUs in the carrier)

 

 

 

HEAT DISSIPATION (MAX.) AT

 

±48 Vdc

 

CO Power Unit (with 16 fully equipped

160 watts (CO Power Unit efficiency is approximately 76%)

cards in the carrier)

 

 

 

PHYSICAL DIMENSIONS

 

CO Power Unit

 

Height

2.4 inches ( 6.2 cm)

Height (including air filter brackets)

3.0 inches ( 7.7 cm)

Width

16.9 inches (43.3 cm)

Depth

13.5 inches (34.6 cm)

Power Module

 

Height

2.4 inches ( 6.2 cm)

Width

8.5 inches (21.8 cm)

Depth

11.7 inches (30.0 cm)

Air Filter

 

Height

0.5 inches ( 1.3 cm)

Width

14.2 inches (36.4 cm)

Depth

5.5 inches (14.1 cm)

 

 

1-4

May 1998

3000-A2-GB41-40

Image 14
Contents Comsphere ±48 Vdc Central Office Power Unit Copyright  1998 Paradyne Corporation. All rights reserved Warranty, Sales, and Service InformationTrademarks Important Safety Instructions Comsphere ±48 Vdc Central Office Power Unit Table of Contents Interface Connections Glossary Index List of Figures Technical Specifications for Central Office CO Power Unit List of TablesAbstract PrefaceObjectives and Reader Assumptions Related DocumentsComsphere ±48 Vdc Central Office Power Unit Introduction OverviewFeatures 2illustrates the CO Power Unit with two power modulesCentral Office CO Power Unit with One Power Module Technical Specifications ±48 VdcEquipment Warranty Support WeightComsphere ±48 Vdc Central Office Power Unit May Installation Considerations Basic Mode of Operation3161 DSU/CSUs Independent Mode of OperationAmbient 3611 DSUs 3551, 3611, Without DBMs DSUs with DBMs DSUs, 3151 and CSUsRedundant Mode of Operation Alarm Forwarding to a 6800 Series NMSProcedure CO Power Unit InstallationInstalling the Optional Second Power Module Installing the Optional Second Power Module Setting the Option Straps Settings for Basic ModeIndependent Mode Settings for Independent ModeInstalling the CO Power Unit Series Carrier Installation ManualCO Power Unit Installation Providing Power to a CO Power Unit Comsphere 3000 Series Carrier RearAMP Procedure GRD Optional Fuses -48V GRD Vdc Power Source a Installing an Sdcp  ProcedureConnecting the Alarm Contacts to a CO Alarm System Ext Leads RPowr Procedure Installation Air Filter and Brackets Installation Optional 11. Air Filter Brackets Installation Comsphere ±48 Vdc Central Office Power Unit May Troubleshooting and Maintenance Indicators and ControlsTroubleshooting Power Module Replacement Instructions Replacing a Power ModulePreventive Maintenance Interface Connections a DC Inputs±48V CO ground return Figure A-2. Connector Housing and Contact Table A-3 CO Alarm System OutputsCO Alarm System Outputs Pin Assignments forNMS Alarm Outputs Figure A-3. NMS Adapter Cable Feature Number 3000-F2-510 Basic mode GlossarySDU Index NMS Index