Paradyne 3600 Series CO Power Unit Installation, Installing the Optional Second Power Module

Page 20

COMSPHERE ±48 Vdc Central Office Power Unit

CO Power Unit Installation

The CO Power Unit is installed at the bottom of the carrier. You will need a large, flat-blade screwdriver to install the CO Power Unit and a medium, flat-blade screwdriver to set the option straps.

NOTE

If you plan to use two power modules in your CO Power Unit, you must install the second power module before proceeding to Step 1. (See the Installing the Optional Second Power Module section.)

The following is an overview of the CO Power Unit installation procedure:

"Procedure

1.Set the option straps on the CO Power Unit's backplane to the desired mode of operation. (See the Setting the Option Straps section.)

If your CO Power Unit has a single power module, you do not need to set the option straps. The option straps are factory set for the Basic mode of operation. However, you should compare the option strap setting on backplane to the strap settings listed in Table 2-2in the Setting the Option Straps section to ensure correct settings.

2.Install the CO Power Unit into the carrier. (See the Installing the CO Power Unit section.)

3.Provide power to the CO Power Unit. (See the Providing Power to a CO Power Unit section.)

4.Install the Shared Diagnostic Control Panel (SDCP) on the carrier in which you installed the CO Power Unit, if desired. (See the Installing an SDCP section.)

5.Connect the alarm contacts for the CO Power Unit to a CO alarm system and/or a Modular 3611 DSU, if desired. (See the Connecting the Alarm Contacts to a CO Alarm System section or the Connecting the Alarm Contacts to a 6800 Series NMS Via a Modular 3611 DSU section.)

Steps 4 and 5 are optional.

Installing the Optional Second Power Module

You can order a second power module for your CO Power Unit. This additional power module allows you to choose between two modes of operation: Redundant or Independent. You must install the optional second power module into the CO power tray before installing the CO Power Unit into the carrier.

To install the optional second power module:

"Procedure

1.Remove the coverplate by loosening the two captive screws on the bottom of the coverplate.

2.Place the second power module in the card guides on the right side of the CO power tray (as viewed from the front of the tray) and then slide power module to the rear of tray. See Figure 2-1.

3.Tighten the two captive screws on the bottom of the power module's faceplate.

2-4

May 1998

3000-A2-GB41-40

Image 20
Contents Comsphere ±48 Vdc Central Office Power Unit Copyright  1998 Paradyne Corporation. All rights reserved Warranty, Sales, and Service InformationTrademarks Important Safety Instructions Comsphere ±48 Vdc Central Office Power Unit Table of Contents Interface Connections Glossary Index List of Figures Technical Specifications for Central Office CO Power Unit List of TablesPreface Objectives and Reader AssumptionsAbstract Related DocumentsComsphere ±48 Vdc Central Office Power Unit Introduction OverviewFeatures 2illustrates the CO Power Unit with two power modulesCentral Office CO Power Unit with One Power Module Technical Specifications ±48 VdcEquipment Warranty Support WeightComsphere ±48 Vdc Central Office Power Unit May Installation Considerations Basic Mode of OperationIndependent Mode of Operation Ambient 3611 DSUs 3551, 3611,3161 DSU/CSUs Without DBMs DSUs with DBMs DSUs, 3151 and CSUsRedundant Mode of Operation Alarm Forwarding to a 6800 Series NMSProcedure CO Power Unit InstallationInstalling the Optional Second Power Module Installing the Optional Second Power Module Setting the Option Straps Settings for Basic ModeIndependent Mode Settings for Independent ModeInstalling the CO Power Unit Series Carrier Installation ManualCO Power Unit Installation Providing Power to a CO Power Unit Comsphere 3000 Series Carrier RearAMP Procedure GRD Optional Fuses -48V GRD Vdc Power Source a Installing an Sdcp  ProcedureConnecting the Alarm Contacts to a CO Alarm System Ext Leads RPowr Procedure Installation Air Filter and Brackets Installation Optional 11. Air Filter Brackets Installation Comsphere ±48 Vdc Central Office Power Unit May Troubleshooting and Maintenance Indicators and ControlsTroubleshooting Power Module Replacement Instructions Replacing a Power ModulePreventive Maintenance Interface Connections a DC Inputs±48V CO ground return Figure A-2. Connector Housing and Contact CO Alarm System Outputs CO Alarm System OutputsTable A-3 Pin Assignments forNMS Alarm Outputs Figure A-3. NMS Adapter Cable Feature Number 3000-F2-510 Basic mode GlossarySDU Index NMS Index