Paradyne 3600 Series, 3611 Providing Power to a CO Power Unit, Comsphere 3000 Series Carrier Rear

Page 26

COMSPHERE ±48 Vdc Central Office Power Unit

BACKPLANE

 

 

 

 

 

CONNECTOR

 

 

 

 

 

CABLE

 

 

 

 

 

ASSEMBLIES

 

 

 

 

 

NETWORK

 

P20

P19

 

 

MANAGEMENT

 

 

 

CONNECTOR

 

 

 

 

 

CAPTIVE

P6

–48VDC B

–48VDC A

P3

CAPTIVE

SCREW

(OUTPUT)

(INPUT)

(INPUT)

(OUTPUT)

SCREW

ALARM B

ALARM A

497-13673-01

 

 

Figure 2-4. COMSPHERE 3000 Series Carrier (Rear)

Providing Power to a CO Power Unit

After the CO Power Unit installation procedure is completed, you must provide power to the unit. There are a number of powering options available depending upon your configuration.

NOTE

The option strap settings are factory set for the Basic mode of operation.

To provide power to the CO Power Unit operating in Basic mode:

"Procedure

1.Use one connector housing (AMP part

number 1-480698-0) and two crimp-type contacts

(AMP part number 350550-1) to attach the connector to your ± 48 Vdc power input cable.

Note that you need a hand crimping tool (AMP part number 90296-2 or equivalent) to build the connector.

(The contacts are crimp type and are intended for use with 20 AWG through 14 AWG wire with a maximum insulation diameter of .130 inches. For additional information, see Appendix A of this guide.)

2.Provide external fusing, if desired. (The fuse shown in Figure 2-5is optional as per your requirements.) The optional fuse should have a rating of 6 amperes, 250 volts, and be a fast-acting type. Use a fuse similar to Littlefuse #312006.

3.Plug the input power cable to either the ±48VDC A connector or the ±48VDC B connector. See Figure 2-5. (The option strap settings for this power option are listed in Table 2-2.)

2-10

May 1998

3000-A2-GB41-40

Image 26
Contents Comsphere ±48 Vdc Central Office Power Unit Copyright  1998 Paradyne Corporation. All rights reserved Warranty, Sales, and Service InformationTrademarks Important Safety Instructions Comsphere ±48 Vdc Central Office Power Unit Table of Contents Interface Connections Glossary Index List of Figures Technical Specifications for Central Office CO Power Unit List of TablesAbstract PrefaceObjectives and Reader Assumptions Related DocumentsComsphere ±48 Vdc Central Office Power Unit Introduction OverviewFeatures 2illustrates the CO Power Unit with two power modulesCentral Office CO Power Unit with One Power Module Technical Specifications ±48 VdcEquipment Warranty Support WeightComsphere ±48 Vdc Central Office Power Unit May Installation Considerations Basic Mode of Operation3161 DSU/CSUs Independent Mode of OperationAmbient 3611 DSUs 3551, 3611, Without DBMs DSUs with DBMs DSUs, 3151 and CSUsRedundant Mode of Operation Alarm Forwarding to a 6800 Series NMSProcedure CO Power Unit InstallationInstalling the Optional Second Power Module Installing the Optional Second Power Module Setting the Option Straps Settings for Basic ModeIndependent Mode Settings for Independent ModeInstalling the CO Power Unit Series Carrier Installation ManualCO Power Unit Installation Providing Power to a CO Power Unit Comsphere 3000 Series Carrier RearAMP Procedure GRD Optional Fuses -48V GRD Vdc Power Source a Installing an Sdcp  ProcedureConnecting the Alarm Contacts to a CO Alarm System Ext Leads RPowr Procedure Installation Air Filter and Brackets Installation Optional 11. Air Filter Brackets Installation Comsphere ±48 Vdc Central Office Power Unit May Troubleshooting and Maintenance Indicators and ControlsTroubleshooting Power Module Replacement Instructions Replacing a Power ModulePreventive Maintenance Interface Connections a DC Inputs±48V CO ground return Figure A-2. Connector Housing and Contact Table A-3 CO Alarm System OutputsCO Alarm System Outputs Pin Assignments forNMS Alarm Outputs Figure A-3. NMS Adapter Cable Feature Number 3000-F2-510 Basic mode GlossarySDU Index NMS Index