COMSPHERE ±48 Vdc Central Office Power Unit

CO Alarm System Outputs

Both major (power) and minor (fan) alarms can be sent to the CO alarm system via the Alarm A and Alarm B output connectors. Figure A-1illustrates these connectors. The connector on the CO Power Unit's backplane is an AMP 5-position single row header. The mating connector is an AMP MTE-type connector (part number 103957-4).

The CO alarm system outputs are relay contact closures. Table A-3lists the pin assignments for the CO alarm system outputs.

 

Table A-3

Pin Assignments for the

CO Alarm System Outputs

 

 

Pin Number

Assigned To ...

 

 

1

Major Alarm (power failure)

 

 

2

Major Alarm (power failure)

 

 

3

No Connection

 

 

4

Minor Alarm (fan failure)

 

 

5

Minor Alarm (fan failure)

 

 

A contact closure is provided between Pin Numbers 1 and 2 to indicate a power failure. A contact closure is provided between Pin Numbers 4 and 5 to indicate a fan failure. Note that a major alarm signal is sent to a CO alarm system upon a failure in either the ± 48V input or low voltage output circuits, and that a minor alarm signal is sent if the fan speed falls below 1900 rpm.

CAUTION

The relay contacts on the CO Power Unit for the CO alarm system have a rating of

0.1amp maximum at 70 Vdc maximum.

A-4

May 1998

3000-A2-GB41-40

Image 46
Contents Comsphere ±48 Vdc Central Office Power Unit Trademarks Warranty, Sales, and Service InformationCopyright  1998 Paradyne Corporation. All rights reserved Important Safety Instructions Comsphere ±48 Vdc Central Office Power Unit Table of Contents Interface Connections Glossary Index List of Figures Technical Specifications for Central Office CO Power Unit List of TablesAbstract PrefaceObjectives and Reader Assumptions Related DocumentsComsphere ±48 Vdc Central Office Power Unit Introduction OverviewFeatures 2illustrates the CO Power Unit with two power modulesCentral Office CO Power Unit with One Power Module Technical Specifications ±48 VdcEquipment Warranty Support WeightComsphere ±48 Vdc Central Office Power Unit May Installation Considerations Basic Mode of Operation3161 DSU/CSUs Independent Mode of OperationAmbient 3611 DSUs 3551, 3611, Without DBMs DSUs with DBMs DSUs, 3151 and CSUsRedundant Mode of Operation Alarm Forwarding to a 6800 Series NMSInstalling the Optional Second Power Module CO Power Unit InstallationProcedure Installing the Optional Second Power Module Setting the Option Straps Settings for Basic ModeIndependent Mode Settings for Independent ModeInstalling the CO Power Unit Series Carrier Installation ManualCO Power Unit Installation Providing Power to a CO Power Unit Comsphere 3000 Series Carrier RearAMP Procedure GRD Optional Fuses -48V GRD Vdc Power Source a Installing an Sdcp  ProcedureConnecting the Alarm Contacts to a CO Alarm System Ext Leads RPowr Procedure Installation Air Filter and Brackets Installation Optional 11. Air Filter Brackets Installation Comsphere ±48 Vdc Central Office Power Unit May Troubleshooting and Maintenance Indicators and ControlsTroubleshooting Power Module Replacement Instructions Replacing a Power ModulePreventive Maintenance Interface Connections a DC Inputs±48V CO ground return Figure A-2. Connector Housing and Contact Table A-3 CO Alarm System OutputsCO Alarm System Outputs Pin Assignments forNMS Alarm Outputs Figure A-3. NMS Adapter Cable Feature Number 3000-F2-510 Basic mode GlossarySDU Index NMS Index