Modbus TCP Remote I/O Communication Module RTU-EN01

7.17 Smart PLC: Counter

Application

Setting up the counter by DCISoft. Once RX#1 counts for 5 times, RY0 will output.

 

 

 

 

Steps

(1)

Set up counter C0: RX#1 counts up 5 times and reaches the target.

(2)

Set up IF-THEN: When the counting reaches the target, RY0 will output.

 

 

 

 

 

1.

Open the setup page and switch to “Smart PLC” page. Further switch to the “Counter” page.

2.

Check to “Enable” Counter 0, select “Count Up”, set Up Bound to “5” and Count Source RX NO. to RX”1”.

 

Click "Apply” to write these settings into RTU-EN01.

3.Switch to “IF-THEN” page and check the “Enable” box. Select “C 0 On” in the IF column and “RY 0 Set” in the THEN column. Click on “Add” to add the settings to the table below and press “OK” to save the settings into RTU-EN01.

44

DVP-PLC Operation Manual

Image 46
Contents RTU-EN01 DVP-0213920-01Page Features Dimension Product Profile LED IndicatorsSetting UP Software Specifications IntroductionDimension 37.460 LED RUN/STOP Switch RJ-45 PIN DefinitionHow to Connect RTU-EN01 to Network Word Devices & Bit Devices in RTU-EN01 Basic Registers BRBR#1 Firmware Version Explanations on BRBR#0 Model Name BR#2 Release Date of the VersionBR#6 Address BR#5 COM2 Communication SettingsBR#9 Error Code BR#7 Number of DI PointsBR#13 TCP Connection Idle Time s BR#12 Communication Delay Time msBR#11 Communication Time-out ms BR#23 Number of Analog I/O ModulesRX#0 ~ #255 External Input Contact BR#50 ~ BR#57 RTC SettingsRY#0 ~ #255 External Output Contact Word Devices & Bit Devices for Timers T #0 Timer#0 Counter #1 ~ #15 Timer 1 ~Word Devices & Bit Devices for Counters C #1 ~ #15 Counter 1 ~#0 RTC Function Codes Supported#1 ~ #15 RTC 1 ~ Coil Discrete inputHolding register You will see the communication module found „ Recording IP address Basic Settings Static User enters the IP address, subnet mask and gateway Network Settings Setting up Time Server IP Filter „ IF-THEN Smart PLC Setting Timer „ RTC Analog Input/Output Modules Modbus TCP Remote I/O Communication Module RTU-EN01 12 I/O Monitoring Table Setting up Gateway Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Security Setting Returning to Default Settings RTU-EN01 DI/DO Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Application Examples DCISoft Smart PLC IF-THENSmart PLC Timer Smart PLC Counter Smart PLC RTC Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01