Modbus TCP Remote I/O Communication Module
5.3 Device Type & Device Address
Discrete input
Device type | Modbus address (Hex) |
| Number | |
RX | 0x0400 ~ 0x04FF |
| 101025 ~ 101280 | 256 |
|
|
| Coil |
|
RY | 0x0500 ~ 0x05FF |
| 001281 ~ 001537 | 256 |
T | 0x1600 ~ 0x160F |
| 005633 ~ 005649 | 16 |
R | 0x1900 ~ 0x190F |
| 006401 ~ 006416 | 16 |
C | 0x1E00 ~ 0x1E0F |
| 007681 ~ 007696 | 16 |
|
| Holding register |
| |
Device type | Modbus address (Hex) |
| Number | |
BR | 0x0000~0x0040 |
| 400001~400064 | 64 |
T | 0x1600~0x160F |
| 405633~405649 | 16 |
C | 0x1E00~0x1E0F |
| 407681~407696 | 16 |
RCR | 0x3000~0x3190 |
| 412289~412689 | 400 |
6 Setting up Software
This section gives instructions on how to set up
6.1 Setting up Communications & Searching for Communication Modules in DCISoft
Broadcast search
1.Open DCISoft on the PC and click on the “IP Search” icon.
16 |