Delta Electronics RTU-EN01 operation manual Virtual COM

Page 48

Modbus TCP Remote I/O Communication Module RTU-EN01

3.Switch to “IF-THEN” page. Check the “Enable” box and select “RT0 On” in the IF column and “RY 0 Set” in the THEN column. Press “Add” to add the settings to the table below.

4.Check “Enable” and select “RT0 Off” in the IF column and “RY 0 Reset” in the THEN column. Press “Add" to add the settings to the table bellow and click on “OK” to save the settings into RTU-EN01.

7.19 Virtual COM

 

The virtual COM converts the data sent to RS-232 port into Ethernet. Virtual COM only

Application

connects to software supporting serial ports, e.g. Delta WPLSoft, VFDSoft, ASDASoft. See

the examples below for how to connect VFD-E series AC motor drive to VFDSoft through by

 

 

virtual COM.

 

 

 

 

(1)

Select user-defined protocol and set the communication parameters for serial

Steps

 

master/slave to the same as the parameters in VFD-E.

(2)

Set up virtual COM.

 

(3)Open Delta VFDSoft, set up the communication format and establish the connection.

1.Setting up virtual COM

„Select Virtual COM for COM2 mode (RS-485) and set up the same communication parameters as those in VFD-E.

46

DVP-PLC Operation Manual

Image 48
Contents RTU-EN01 DVP-0213920-01Page Features Dimension Product Profile LED IndicatorsSetting UP Software Specifications IntroductionDimension 37.460 LED RUN/STOP Switch RJ-45 PIN DefinitionHow to Connect RTU-EN01 to Network Word Devices & Bit Devices in RTU-EN01 Basic Registers BRExplanations on BR BR#0 Model NameBR#1 Firmware Version BR#2 Release Date of the VersionBR#5 COM2 Communication Settings BR#9 Error CodeBR#6 Address BR#7 Number of DI PointsBR#12 Communication Delay Time ms BR#11 Communication Time-out msBR#13 TCP Connection Idle Time s BR#23 Number of Analog I/O ModulesBR#50 ~ BR#57 RTC Settings RX#0 ~ #255 External Input ContactRY#0 ~ #255 External Output Contact Word Devices & Bit Devices for Timers T #0 Timer#1 ~ #15 Timer 1 ~ Word Devices & Bit Devices for Counters C#0 Counter #1 ~ #15 Counter 1 ~Function Codes Supported #0 RTC#1 ~ #15 RTC 1 ~ Discrete input CoilHolding register You will see the communication module found „ Recording IP address Basic Settings Static User enters the IP address, subnet mask and gateway Network Settings Setting up Time Server IP Filter „ IF-THEN Smart PLC Setting Timer „ RTC Analog Input/Output Modules Modbus TCP Remote I/O Communication Module RTU-EN01 12 I/O Monitoring Table Setting up Gateway Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Security Setting Returning to Default Settings RTU-EN01 DI/DO Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Application Examples DCISoft Smart PLC IF-THENSmart PLC Timer Smart PLC Counter Smart PLC RTC Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01