Delta Electronics Complete Guide to Modbus TCP Remote I/O Communication with RTU-EN01

Page 10

Modbus TCP Remote I/O Communication Module RTU-EN01

DVPEN01-SL DVP28SV

DVP28SV

RUN

STOP

Ethernet

 

 

TS8 0

16SP

DA4 0

-PV D

DVP-

-PV D

COM2

 

 

RTU-EN01

DI/DO

 

PC

CT40

TP4 0

02DA

-PV D

-PV D

DVP-

AI/AO

4

Word Devices & Bit Devices in RTU-EN01

 

 

4.1

Basic Registers (BR)

 

 

 

 

 

 

 

 

 

 

 

BR#

Attribute

Content

Explanation

Default

Latched

 

0

R

Model name

Set up by the system; read only. The model code of

H’0600

YES

 

RTU-EN01= H’0600.

 

 

 

 

 

 

 

1

R

Firmware version

Displaying the current firmware verision in hex, e.g. V1.2 is

 

YES

 

indicated as high byte = 0x01 and low byte = 0x20.

 

 

 

 

 

 

 

 

 

 

 

Displaying the data in decimal form. 10,000s digit and 1,000s

 

 

 

 

 

 

digit are for “month”; 100s digit and 10s digit are for “day”. For

 

 

 

2

R

Release date of the

1s digit: 0 = morning; 1 = afternoon.

 

YES

 

version

 

 

 

 

 

Example: 12191 indicates the version released in the afternoon

 

 

 

 

 

 

 

 

 

 

 

 

of December 19.

 

 

 

3

R/W

Start/Stop PLC

 

 

NO

 

function

 

 

 

 

 

 

 

 

 

4

 

Reserved

.

 

NO

 

 

 

 

 

 

 

 

 

 

COM2

RS-485 communication settings. Please refer to the table of

 

 

 

5

R/W

communication

H’0368

YES

 

baud rate setting and communication format setting.

 

 

 

settings

 

 

 

 

 

 

 

 

 

6

R/W

Address

For setting up the station address

K’1

YES

 

 

 

 

 

 

 

 

7

R

Number of DI points

Range: 0 ~ 256

 

NO

 

 

 

 

 

 

 

 

8

R

Number of DO points

Range: 0 ~ 256

 

NO

 

 

 

 

 

 

 

 

9

R

Error code

Displaying the errors. Please refer to the table of error codes.

 

NO

 

 

 

 

 

 

 

 

10

 

Reserved

 

 

NO

 

 

 

 

 

 

 

 

11

R/W

Communication

For setting up the communication time-out (ms) in Modbus

K’5000

YES

 

time-out

TCP mode.

 

 

 

 

 

 

12

R/W

Communication delay

For setting up the minimum interval time between every

K’0

YES

 

time

communication datum.

 

 

 

 

 

 

13

R/W

TCP connection idle

For setting up idle time for TCP communication. Unit: second

K’30

YES

 

time

 

 

 

 

 

 

 

14 ~ 22

 

Reserved

 

 

NO

 

 

 

 

 

 

 

 

23

R

Number of analog I/O

Max. 8

 

NO

 

 

 

modules

 

 

 

8

DVP-PLC Operation Manual

Image 10
Contents RTU-EN01 DVP-0213920-01Page Features Dimension Product Profile LED IndicatorsSetting UP Software Specifications IntroductionDimension 37.460 LED RUN/STOP Switch RJ-45 PIN DefinitionHow to Connect RTU-EN01 to Network Word Devices & Bit Devices in RTU-EN01 Basic Registers BRBR#1 Firmware Version Explanations on BRBR#0 Model Name BR#2 Release Date of the VersionBR#6 Address BR#5 COM2 Communication SettingsBR#9 Error Code BR#7 Number of DI PointsBR#13 TCP Connection Idle Time s BR#12 Communication Delay Time msBR#11 Communication Time-out ms BR#23 Number of Analog I/O ModulesRX#0 ~ #255 External Input Contact BR#50 ~ BR#57 RTC SettingsRY#0 ~ #255 External Output Contact Word Devices & Bit Devices for Timers T #0 Timer#0 Counter #1 ~ #15 Timer 1 ~Word Devices & Bit Devices for Counters C #1 ~ #15 Counter 1 ~#0 RTC Function Codes Supported#1 ~ #15 RTC 1 ~ Coil Discrete inputHolding register You will see the communication module found „ Recording IP address Basic Settings Static User enters the IP address, subnet mask and gateway Network Settings Setting up Time Server IP Filter „ IF-THEN Smart PLC Setting Timer „ RTC Analog Input/Output Modules Modbus TCP Remote I/O Communication Module RTU-EN01 12 I/O Monitoring Table Setting up Gateway Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Security Setting Returning to Default Settings RTU-EN01 DI/DO Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Application Examples DCISoft Smart PLC IF-THENSmart PLC Timer Smart PLC Counter Smart PLC RTC Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01