Delta Electronics RTU-EN01 operation manual Analog Input/Output Modules

Page 29

Modbus TCP Remote I/O Communication Module RTU-EN01

1.Enable:

Decide whether to trigger the RTC in this column.

2.Cyclic:

Decide to trigger the RTC only once, or trigger it on a daily, weekly or monthly basis.

3.Output auto-reset:

After the RTC is triggered, decide whether to retain the output for a period of time and reset the RTC automatically. R (Coil) will be OFF when the time for reset is reached.

4.Auto-reset time, Unit:

If you select to auto-reset the RTC, the bit device in RTC will retain the output for a period of time. Range: 1s ~ 24hr.

Range for second as unit: 1 ~ 32,767

Range for minute as unit: 1 ~ 3,600

Range for hour as unit: 1 ~ 24

5.Year, Month, Day, Hour, Minute, Second, Week:

The time to trigger the RTC. If you would like to trigger it only once, only Year, Month, Day, Hour, Minute and Second need to be set. If you would like to trigger on a daily basis, only Hour, Minute and Second need to be set. If you would like the RTC to be triggered on a weekly basis, you only need to set up Week, Hour, Minute and Second. If the RTC is triggered monthly, set up only Day, Hour, Minute and Second.

6.11Analog Input/Output Modules

RTU-EN01 offers control registers (CR) for analog I/O modules and is built-in with mapping tables of CR for read/write. The user can check the CR to be read/written and use Delta’s communication module DVPEN01-SL to map the CR directly to D registers in DVP-SV series PLC and read/write the D register through PLC program, controlling the analog I/O module connected to RTU-EN01. RTU-EN01 supports maximum 64 data reading/writing.

fThis function works with DVPEN01-SL of firmware V2.0 or versions above.

„Analog I/O modules

DVP-PLC Operation Manual

27

Image 29
Contents DVP-0213920-01 RTU-EN01Page Dimension Product Profile LED Indicators FeaturesSetting UP Software Introduction SpecificationsDimension 37.460 LED RJ-45 PIN Definition RUN/STOP SwitchHow to Connect RTU-EN01 to Network Basic Registers BR Word Devices & Bit Devices in RTU-EN01BR#0 Model Name Explanations on BRBR#1 Firmware Version BR#2 Release Date of the VersionBR#9 Error Code BR#5 COM2 Communication SettingsBR#6 Address BR#7 Number of DI PointsBR#11 Communication Time-out ms BR#12 Communication Delay Time msBR#13 TCP Connection Idle Time s BR#23 Number of Analog I/O ModulesRY#0 ~ #255 External Output Contact BR#50 ~ BR#57 RTC SettingsRX#0 ~ #255 External Input Contact #0 Timer Word Devices & Bit Devices for Timers TWord Devices & Bit Devices for Counters C #1 ~ #15 Timer 1 ~#0 Counter #1 ~ #15 Counter 1 ~#1 ~ #15 RTC 1 ~ Function Codes Supported#0 RTC Holding register Discrete inputCoil You will see the communication module found „ Recording IP address Basic Settings Static User enters the IP address, subnet mask and gateway Network Settings Setting up Time Server IP Filter „ IF-THEN Smart PLC Setting Timer „ RTC Analog Input/Output Modules Modbus TCP Remote I/O Communication Module RTU-EN01 12 I/O Monitoring Table Setting up Gateway Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Security Setting Returning to Default Settings RTU-EN01 DI/DO Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Smart PLC IF-THEN Application Examples DCISoftSmart PLC Timer Smart PLC Counter Smart PLC RTC Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01