Delta Electronics RTU-EN01 operation manual „ If-Then

Page 26

Modbus TCP Remote I/O Communication Module RTU-EN01

Check the box to enable IP filter.

2.Begin IP address:

Start IP addresses allowed to establish connection. Max. 8 IPs are allowed.

3.End IP address:

End IP addresses allowed to establish connection. Max. 8 IPs are allowed.

6.7 Smart PLC Setting: IF-THEN

RTU-EN01 has the independent Smart PLC function. IF-THEN is able to execute the corresponding function of the condition set up by the user and combine with the functions of counter, timer, RTC, digital I/O points and analog I/O modules. You can use AND or OR as the trigger condition. There are 16 IF-THEN functions in RTU-EN01.

„IF-THEN

1.Enable:

Check the box to enable IF-THEN.

2.IF:

For the trigger condition, you can select bit devices RX, RY, C, T, RT or word device RCR and set them to ON, OFF, Rising, Falling, >, <, =, <>, >= or <=. The trigger condition can be AND or OR. When the device is a register, the allowed trigger range will be K-32,768 ~ K32,767.

3.THEN:

For the execution, you can select bit devices RY, C, T, RT or word device RCR and set them to Set, Reset, Toggle or set up a value for them. Please refer to the explanations on IF#13 ~ IF#24. When the device is a register, the allowed trigger range will be K-32,768 ~ K32,767.

4.Add, Modify, Clear, Delete:

All the settings above can be added to the IF-THEN table below, or you can modify, clear or delete the settings.

5.Up, Down:

24

DVP-PLC Operation Manual

Image 26
Contents RTU-EN01 DVP-0213920-01Page Features Dimension Product Profile LED IndicatorsSetting UP Software Specifications IntroductionDimension 37.460 LED RUN/STOP Switch RJ-45 PIN DefinitionHow to Connect RTU-EN01 to Network Word Devices & Bit Devices in RTU-EN01 Basic Registers BRBR#1 Firmware Version Explanations on BRBR#0 Model Name BR#2 Release Date of the VersionBR#6 Address BR#5 COM2 Communication SettingsBR#9 Error Code BR#7 Number of DI PointsBR#13 TCP Connection Idle Time s BR#12 Communication Delay Time msBR#11 Communication Time-out ms BR#23 Number of Analog I/O ModulesRY#0 ~ #255 External Output Contact BR#50 ~ BR#57 RTC SettingsRX#0 ~ #255 External Input Contact Word Devices & Bit Devices for Timers T #0 Timer#0 Counter #1 ~ #15 Timer 1 ~Word Devices & Bit Devices for Counters C #1 ~ #15 Counter 1 ~#1 ~ #15 RTC 1 ~ Function Codes Supported#0 RTC Holding register Discrete inputCoil You will see the communication module found „ Recording IP address Basic Settings Static User enters the IP address, subnet mask and gateway Network Settings Setting up Time Server IP Filter „ IF-THEN Smart PLC Setting Timer „ RTC Analog Input/Output Modules Modbus TCP Remote I/O Communication Module RTU-EN01 12 I/O Monitoring Table Setting up Gateway Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Security Setting Returning to Default Settings RTU-EN01 DI/DO Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Application Examples DCISoft Smart PLC IF-THENSmart PLC Timer Smart PLC Counter Smart PLC RTC Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01