Delta Electronics RTU-EN01 BR#50 ~ BR#57 RTC Settings, RX#0 ~ #255 External Input Contact

Page 14

Modbus TCP Remote I/O Communication Module RTU-EN01

BR#50 ~ BR#57: RTC Settings

Explanations:

For setting up the real-time clock (RTC). When BR#9 = 1, RTU-EN01 will stop to update the RTC values to BR#10 ~ #16. Once the setup is completed, RTU-EN01 will set BR#9 to 0.

Allowed range for RTC: 1970/01/01 00:00:00 ~ 2037/12/31 23:59:59

BR#9

0No action

1RTC stops

2RTC being set

4.3External Input Contacts (RX)

RX#

Attribute

Content

Explanation

Default

Latched

0 ~ 255

R/W

External input contact

Input points on analog I/O module

OFF

NO

 

 

 

 

 

 

Symbol “R” refers to ready only; “R/W” refers to read and write.

RX#0 ~ #255: External Input Contact

Explanations:

The right-side extension interface on RTU-EN01 is able to connect to DVP-Slim series digital I/O modules. RTU-EN01 supports maximum 256 I/O points.

4.4 External Output Contacts (RY)

RY#

Attribute

Content

Explanation

Default

Latched

0 ~ 255

R/W

External output contact

Output points on analog I/O module

OFF

NO

 

 

 

 

 

 

Symbol “R” refers to ready only; “R/W” refers to read and write.

RY#0 ~ #255: External Output Contact

Explanations:

The right-side extension interface on RTU-EN01 is able to connect to DVP-Slim series digital I/O modules. RTU-EN01 supports maximum 256 I/O points.

4.5 Control Register for Extension Modules (RCR)

RCR#

Attribute

 

Content

Explanation

Default

Latched

0 ~ 49

R/W

The 1st

analog I/O

Control register for the 1st analog I/O

--

NO

module

 

module

 

 

 

 

 

 

50

~ 99

R/W

The 2nd analog I/O

Control register for the 2nd analog I/O

--

NO

module

 

module

 

 

 

 

 

 

100

~ 149

R/W

The 3rd

analog I/O

Control register for the 3rd analog I/O

--

NO

module

 

module

 

 

 

 

 

 

150

~ 199

R/W

The 4th

analog I/O

Control register for the 4th analog I/O

--

NO

module

 

module

 

 

 

 

 

 

12

DVP-PLC Operation Manual

Image 14
Contents RTU-EN01 DVP-0213920-01Page Features Dimension Product Profile LED IndicatorsSetting UP Software Specifications IntroductionDimension 37.460 LED RUN/STOP Switch RJ-45 PIN DefinitionHow to Connect RTU-EN01 to Network Word Devices & Bit Devices in RTU-EN01 Basic Registers BRBR#1 Firmware Version Explanations on BRBR#0 Model Name BR#2 Release Date of the VersionBR#6 Address BR#5 COM2 Communication SettingsBR#9 Error Code BR#7 Number of DI PointsBR#13 TCP Connection Idle Time s BR#12 Communication Delay Time msBR#11 Communication Time-out ms BR#23 Number of Analog I/O ModulesRY#0 ~ #255 External Output Contact BR#50 ~ BR#57 RTC SettingsRX#0 ~ #255 External Input Contact Word Devices & Bit Devices for Timers T #0 Timer#0 Counter #1 ~ #15 Timer 1 ~Word Devices & Bit Devices for Counters C #1 ~ #15 Counter 1 ~#1 ~ #15 RTC 1 ~ Function Codes Supported#0 RTC Holding register Discrete inputCoil You will see the communication module found „ Recording IP address Basic Settings Static User enters the IP address, subnet mask and gateway Network Settings Setting up Time Server IP Filter „ IF-THEN Smart PLC Setting Timer „ RTC Analog Input/Output Modules Modbus TCP Remote I/O Communication Module RTU-EN01 12 I/O Monitoring Table Setting up Gateway Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Security Setting Returning to Default Settings RTU-EN01 DI/DO Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Application Examples DCISoft Smart PLC IF-THENSmart PLC Timer Smart PLC Counter Smart PLC RTC Virtual COM Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01 Modbus TCP Remote I/O Communication Module RTU-EN01