American Power Conversion Bypass Static manual UPS Shutdown screen

Page 18

UPS Shutdown screen

Normal

Normal

UPS Shutdown

5.40 PM

Initiate transfer to static bypass

Initiate transfer

Close breaker Q3

Load will be on manual bypass

Open breaker Q5

SSW input

Push UPS "OFF" button

UPS power down

Open breaker Q2

UPS output

Open battery breakers Q7 and Q8

Isolate UPS from battery

Open breaker Q1

UPS input

The UPS Shutdown screen shows a list of actions, which need to be completed in order to shut down the UPS. The actions are initially indicated in red to show that they have not yet been completed. A yellow bar will highlight the actions in the order in which they need to be completed. As actions are completed they will change to green.

The Start-Up procedure is described in “System Shutdown from Online to Manual Bypass Operation” .

12

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

Image 18
Contents Symmetra MW UPS Page Contents Operation Modes Alarms/Troubleshooting Page Safety Symbols used in this guideUser Safety Screen symbols Display Symbols and ButtonsNavigation symbols UPS DisplayButtons EMOUPS Summary Screen UPS SummaryInput Summary Screens ~ ~Output Summary Screens Normal Output SummaryBypass Summary Screens ~ ~Battery Summary Screens Curve shows the batteryOperation Screen OperationUPS Start-Up Screen UPS StartupUPS Shutdown screen UPS ShutdownOnline to Static Bypass Screen Online to Static BypassStatic Bypass to Online Screen Network Configuration Screens Network Settings screenNetwork Settings Mail Settings screen Mail SettingsSnmp Settings screen Snmp SettingsRemote Monitoring Service Settings screen Remote Monitoring Service SettingsAPC ISX Manager Settings screen APC ISX Manager SettingsUser Configuration Screens Touch-Screen Settings screenPassword Settings screen Modbus Settings screenRegional Settings screen Battery Test screenUPS Display User Configuration Screens AlarmSevereNormal EventLogLog Event Log ScreenPredictive Maintenance Screens Inverter DC Capacitors screenInverter DC Capacitors Inverter AC Capacitors screen Inverter AC CapacitorsTop Fans screen Top FansInverter Fans screen Inverter FansMain Static Switch Fans screen Main Static Switch FansPage Operation Modes On-line OperationBattery Operation Bypass Operation Manual Bypass Operation Select Operation Configuration Select Start-up System Start-Up from Manual Bypass OperationOperation Modes System Start-Up from Manual Bypass Operation Select Operation Configuration System Shutdown from Online to Manual Bypass OperationPage Transfer from Online to Static Bypass Operation Online to Static BypassTransfer from Static Bypass to Online Operation Select Static Bypass Online on Operation screenInfo Alarms/TroubleshootingAlarm Types SevereView active alarms Active AlarmsAPC Symmetra MW Remote Display Starting web-based remote session Warranty Factory WarrantyLife Support Policy Appendix a Air Filter ExchangeAppendix a Air Filter Exchange Page APC Worldwide Customer Support