American Power Conversion Bypass Static manual System Start-Up from Manual Bypass Operation

Page 41

System Start-Up from Manual Bypass Operation

If the UPS has been operating in manual bypass operation and no power is connected to the UPS, the UPS display will be inactive. To re-start the system from manual bypass and achieve on-line operation, close Q1 in the external maintenance bypass panel. This will power up the internal power supply. Wait for the display to become active and follow the screen-prompted instructions.

CAUTION!

Follow these instructions carefully. Failure to do so could result in equipment damage.

Manual bypass/Off

Normal

UPS Summary

0:00 AM

Q2

~ ~

Q7

Q8

Select Operation/

Configuration

Select Start-up

Manual Bypass/Off

Normal

Operation

5.40 PM

Startup

Transfer from manual bypass to online

Shutdown

Transfer from online to manual bypass

Online Static Bypass

Transfer from online to static bypass

Static Bypass Online

Transfer from static bypass to online

Network Configuration

 

User Configuration

 

View Event Log

 

Predictive Maintenance

 

Follow the start-up instructions on the screen.

Manual bypass/Off

Normal

UPS Startup

5.40 PM

Close Q1

Display will be off until Q1 closed

Close breaker Q5

SSW input

 

 

Charge DC Capacitors

Initiate Charge

Close battery breakers Q7 and Q8

Connect battery

Close breaker Q2

UPS output

Initiate transfer to static bypass

Initiate transfer

Open breaker Q3

Manual bypass

Push UPS "ON" button

UPS will power up

Active commands initially appear in red. Once a command has been carried out successfully, its text will change to green. Important: After pressing “Initiate charge” in step 2, wait until the green lights go on alongside battery breakers Q7 and Q8 on front of the Battery Breaker Box before closing the breakers.

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

35

Image 41
Contents Symmetra MW UPS Page Contents Operation Modes Alarms/Troubleshooting Page Symbols used in this guide SafetyUser Safety Navigation symbols Display Symbols and ButtonsScreen symbols UPS DisplayEMO ButtonsUPS Summary UPS Summary Screen~ ~ Input Summary ScreensNormal Output Summary Output Summary Screens~ ~ Bypass Summary ScreensCurve shows the battery Battery Summary ScreensOperation Operation ScreenUPS Startup UPS Start-Up ScreenUPS Shutdown UPS Shutdown screenOnline to Static Bypass Online to Static Bypass ScreenStatic Bypass to Online Screen Network Settings Network Configuration ScreensNetwork Settings screen Mail Settings Mail Settings screenSnmp Settings Snmp Settings screenRemote Monitoring Service Settings Remote Monitoring Service Settings screenAPC ISX Manager Settings APC ISX Manager Settings screenTouch-Screen Settings screen User Configuration ScreensModbus Settings screen Password Settings screenBattery Test screen Regional Settings screenUPS Display User Configuration Screens Event Log Screen AlarmSevereNormal EventLogLogInverter DC Capacitors Predictive Maintenance ScreensInverter DC Capacitors screen Inverter AC Capacitors Inverter AC Capacitors screenTop Fans Top Fans screenInverter Fans Inverter Fans screenMain Static Switch Fans Main Static Switch Fans screenPage On-line Operation Operation ModesBattery Operation Bypass Operation Manual Bypass Operation System Start-Up from Manual Bypass Operation Select Operation Configuration Select Start-upOperation Modes System Start-Up from Manual Bypass Operation System Shutdown from Online to Manual Bypass Operation Select Operation ConfigurationPage Online to Static Bypass Transfer from Online to Static Bypass OperationSelect Static Bypass Online on Operation screen Transfer from Static Bypass to Online OperationAlarm Types Alarms/TroubleshootingInfo SevereActive Alarms View active alarmsAPC Symmetra MW Remote Display Starting web-based remote session Factory Warranty WarrantyLife Support Policy Air Filter Exchange Appendix aAppendix a Air Filter Exchange Page APC Worldwide Customer Support