American Power Conversion Bypass Static System Shutdown from Online to Manual Bypass Operation

Page 43

System Shutdown from Online to Manual Bypass Operation

To shut down the UPS (transfer from on-line operation to manual bypass operation), follow the screen-prompted instructions as illustrated.

CAUTION!

Do not open Q3 when the UPS is in manual bypass operation, as this action may result in a load drop or a failure of the UPS to support the load.

Normal

UPS Summary

0:00 AM

~ ~

Q2

Q7 Q8

Select Operation/

Configuration

Normal

Normal

Operation

5.40 PM

Startup

Transfer from manual bypass to online

Shutdown

Transfer from online to manual bypass

Online Static Bypass

Transfer from online to static bypass

Static Bypass Online

Transfer from static bypass to online

Select Shutdown

Network Configuration

User Configuration

View Event Log

Predictive Maintenance

Follow the shut-down instructions on the screen.

Normal

Normal

UPS Shutdown

5.40 PM

Initiate transfer to static bypass

Initiate transfer

Close breaker Q3

Load will be on manual bypass

All instructions initially appear in red. Once a command has been carried out successfully, its text will change to green.

Open breaker Q5

SSW input

Push UPS "OFF" button

UPS power down

Open breaker Q2

UPS output

Open battery breakers Q7 and Q8

Isolate UPS from battery

Open breaker Q1

UPS input

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

37

Image 43
Contents Symmetra MW UPS Page Contents Operation Modes Alarms/Troubleshooting Page Symbols used in this guide SafetyUser Safety UPS Display Display Symbols and ButtonsNavigation symbols Screen symbolsEMO ButtonsUPS Summary UPS Summary Screen~ ~ Input Summary ScreensNormal Output Summary Output Summary Screens~ ~ Bypass Summary ScreensCurve shows the battery Battery Summary ScreensOperation Operation ScreenUPS Startup UPS Start-Up ScreenUPS Shutdown UPS Shutdown screenOnline to Static Bypass Online to Static Bypass ScreenStatic Bypass to Online Screen Network Settings screen Network Configuration ScreensNetwork Settings Mail Settings Mail Settings screenSnmp Settings Snmp Settings screenRemote Monitoring Service Settings Remote Monitoring Service Settings screenAPC ISX Manager Settings APC ISX Manager Settings screenTouch-Screen Settings screen User Configuration ScreensModbus Settings screen Password Settings screenBattery Test screen Regional Settings screenUPS Display User Configuration Screens Event Log Screen AlarmSevereNormal EventLogLogInverter DC Capacitors screen Predictive Maintenance ScreensInverter DC Capacitors Inverter AC Capacitors Inverter AC Capacitors screenTop Fans Top Fans screenInverter Fans Inverter Fans screenMain Static Switch Fans Main Static Switch Fans screenPage On-line Operation Operation ModesBattery Operation Bypass Operation Manual Bypass Operation System Start-Up from Manual Bypass Operation Select Operation Configuration Select Start-upOperation Modes System Start-Up from Manual Bypass Operation System Shutdown from Online to Manual Bypass Operation Select Operation ConfigurationPage Online to Static Bypass Transfer from Online to Static Bypass OperationSelect Static Bypass Online on Operation screen Transfer from Static Bypass to Online OperationSevere Alarms/TroubleshootingAlarm Types InfoActive Alarms View active alarmsAPC Symmetra MW Remote Display Starting web-based remote session Factory Warranty WarrantyLife Support Policy Air Filter Exchange Appendix aAppendix a Air Filter Exchange Page APC Worldwide Customer Support