American Power Conversion Bypass Static manual Battery Operation

Page 38

Battery Operation

During battery operation, the load is supported by the inverters. The inverters are supplied by battery power, ensuring uninterrupted support to the load.

While the UPS is running in battery operation, a single-line diagram will appear on the screen with a green line indicating the power flow from the batteries through the main inverter to the load for as long as the batteries are energized.

CAUTION!

Do not open Q2, Q7 or Q8 when the UPS is in battery operation, as this action may result in a load drop or a failure of the UPS to support the load.

Bypass Static Switch

Delta inverter

Main inverter

Battery

Breaker Identification

Q1

UPS input breaker

Q5

Static bypass input breaker

 

 

 

 

Q2

UPS output breaker

Q7

Battery breaker 1

 

 

 

 

Q3

Manual bypass breaker

Q8

Battery breaker 2

 

 

 

 

Only operate a breaker when the associated breaker lamp is on.

Note

32

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

Image 38
Contents Symmetra MW UPS Page Contents Operation Modes Alarms/Troubleshooting Page Safety Symbols used in this guideUser Safety Screen symbols Display Symbols and ButtonsNavigation symbols UPS DisplayButtons EMOUPS Summary Screen UPS SummaryInput Summary Screens ~ ~Output Summary Screens Normal Output SummaryBypass Summary Screens ~ ~Battery Summary Screens Curve shows the batteryOperation Screen OperationUPS Start-Up Screen UPS StartupUPS Shutdown screen UPS ShutdownOnline to Static Bypass Screen Online to Static BypassStatic Bypass to Online Screen Network Settings Network Configuration ScreensNetwork Settings screen Mail Settings screen Mail SettingsSnmp Settings screen Snmp SettingsRemote Monitoring Service Settings screen Remote Monitoring Service SettingsAPC ISX Manager Settings screen APC ISX Manager SettingsUser Configuration Screens Touch-Screen Settings screenPassword Settings screen Modbus Settings screenRegional Settings screen Battery Test screenUPS Display User Configuration Screens AlarmSevereNormal EventLogLog Event Log ScreenInverter DC Capacitors Predictive Maintenance ScreensInverter DC Capacitors screen Inverter AC Capacitors screen Inverter AC CapacitorsTop Fans screen Top FansInverter Fans screen Inverter FansMain Static Switch Fans screen Main Static Switch FansPage Operation Modes On-line OperationBattery Operation Bypass Operation Manual Bypass Operation Select Operation Configuration Select Start-up System Start-Up from Manual Bypass OperationOperation Modes System Start-Up from Manual Bypass Operation Select Operation Configuration System Shutdown from Online to Manual Bypass OperationPage Transfer from Online to Static Bypass Operation Online to Static BypassTransfer from Static Bypass to Online Operation Select Static Bypass Online on Operation screenInfo Alarms/TroubleshootingAlarm Types SevereView active alarms Active AlarmsAPC Symmetra MW Remote Display Starting web-based remote session Warranty Factory WarrantyLife Support Policy Appendix a Air Filter ExchangeAppendix a Air Filter Exchange Page APC Worldwide Customer Support