Battery Operation
During battery operation, the load is supported by the inverters. The inverters are supplied by battery power, ensuring uninterrupted support to the load.
While the UPS is running in battery operation, a
CAUTION!
Do not open Q2, Q7 or Q8 when the UPS is in battery operation, as this action may result in a load drop or a failure of the UPS to support the load.
Bypass Static Switch
Delta inverter
Main inverter
Battery
Breaker Identification
Q1 | UPS input breaker | Q5 | Static bypass input breaker |
|
|
|
|
Q2 | UPS output breaker | Q7 | Battery breaker 1 |
|
|
|
|
Q3 | Manual bypass breaker | Q8 | Battery breaker 2 |
|
|
|
|
Only operate a breaker when the associated breaker lamp is on.
Note
32 | Symmetra® MW with Internal Bypass Static Switch - User Guide - |