American Power Conversion Bypass Static manual

Page 42

Operation Modes: System Start-Up from Manual Bypass Operation

System Start-Up from Manual Bypass to Online Operation of single mains/utility

system - Step-by-Step

1.Close Q1 in the external maintenance bypass panel to power up the internal power supply. Wait for the display to become active.

2.Press Operation/Configuration on the UPS Summary screen on the UPS display.

3.Press Startup on Operation screen.

4.Press “Initiate Charge” on the UPS display to initiate the charging of the UPS DC capacitors.

5.When the green lights H7 and H8 are illuminated, close battery breakers Q7 and Q8 to connect the battery system.

6.Close Q2 breaker.

7.Press “Initiate Transfer” on the UPS display to transfer to Static Bypass Operation.

8.Open maintenance bypass breaker Q3.

9.Push ON button on the UPS to transfer to Online Operation

System Start-Up from Manual Bypass to Online Operation of dual mains/utility

system - Step-by-Step

1.Close Q1 and Q5 in the external maintenance bypass panel to power up the internal power supply. Wait for the display to become active.

2.Press Operation/Configuration on the UPS Summary screen on the UPS display.

3.Press Startup on Operation screen.

4.Press “Initiate Charge” on the UPS display to initiate the charging of the UPS DC capacitors.

5.When the green lights H7 and H8 are illuminated, close battery breakers Q7 and Q8 to connect the battery system.

6.Close Q2 breaker.

7.Press “Initiate Transfer” on the UPS display to transfer to Static Bypass Operation.

8.Open maintenance bypass breaker Q3.

9.Push ON button on the UPS to transfer to Online Operation

36

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

Image 42
Contents Symmetra MW UPS Page Contents Operation Modes Alarms/Troubleshooting Page Safety Symbols used in this guideUser Safety Screen symbols Display Symbols and ButtonsNavigation symbols UPS DisplayButtons EMOUPS Summary Screen UPS SummaryInput Summary Screens ~ ~Output Summary Screens Normal Output SummaryBypass Summary Screens ~ ~Battery Summary Screens Curve shows the batteryOperation Screen OperationUPS Start-Up Screen UPS StartupUPS Shutdown screen UPS ShutdownOnline to Static Bypass Screen Online to Static BypassStatic Bypass to Online Screen Network Configuration Screens Network Settings screenNetwork Settings Mail Settings screen Mail SettingsSnmp Settings screen Snmp SettingsRemote Monitoring Service Settings screen Remote Monitoring Service SettingsAPC ISX Manager Settings screen APC ISX Manager SettingsUser Configuration Screens Touch-Screen Settings screenPassword Settings screen Modbus Settings screenRegional Settings screen Battery Test screenUPS Display User Configuration Screens AlarmSevereNormal EventLogLog Event Log ScreenPredictive Maintenance Screens Inverter DC Capacitors screenInverter DC Capacitors Inverter AC Capacitors screen Inverter AC CapacitorsTop Fans screen Top FansInverter Fans screen Inverter FansMain Static Switch Fans screen Main Static Switch FansPage Operation Modes On-line OperationBattery Operation Bypass Operation Manual Bypass Operation Select Operation Configuration Select Start-up System Start-Up from Manual Bypass OperationOperation Modes System Start-Up from Manual Bypass Operation Select Operation Configuration System Shutdown from Online to Manual Bypass OperationPage Transfer from Online to Static Bypass Operation Online to Static BypassTransfer from Static Bypass to Online Operation Select Static Bypass Online on Operation screenInfo Alarms/TroubleshootingAlarm Types SevereView active alarms Active AlarmsAPC Symmetra MW Remote Display Starting web-based remote session Warranty Factory WarrantyLife Support Policy Appendix a Air Filter ExchangeAppendix a Air Filter Exchange Page APC Worldwide Customer Support