UPS Display: User Configuration Screens

Battery monitor test: Setting this value to True results in an automatic battery monitor test being performed at regular intervals specified by the Service Engineer. The three options are:

Auto battery test - every (N) week(s).

Auto battery test - on one day of the week.

Auto battery test - at a specific time of the day.

Battery capacity test: Setting this value to True results in the batteries being discharged until a Battery Low Voltage Level is reached. This test can only be performed manually. The test is used to cycle the batteries in order to calibrate the backup time with the current load and battery modules installed.

Battery monitor reset: In the event of a weak battery or another battery problem, use this button to reset the battery monitor.

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

23

Image 29
Contents Symmetra MW UPS Page Contents Operation Modes Alarms/Troubleshooting Page Symbols used in this guide SafetyUser Safety Navigation symbols Display Symbols and ButtonsScreen symbols UPS DisplayEMO ButtonsUPS Summary UPS Summary Screen~ ~ Input Summary ScreensNormal Output Summary Output Summary Screens~ ~ Bypass Summary ScreensCurve shows the battery Battery Summary ScreensOperation Operation ScreenUPS Startup UPS Start-Up ScreenUPS Shutdown UPS Shutdown screenOnline to Static Bypass Online to Static Bypass ScreenStatic Bypass to Online Screen Network Settings Network Configuration ScreensNetwork Settings screen Mail Settings Mail Settings screenSnmp Settings Snmp Settings screenRemote Monitoring Service Settings Remote Monitoring Service Settings screenAPC ISX Manager Settings APC ISX Manager Settings screenTouch-Screen Settings screen User Configuration ScreensModbus Settings screen Password Settings screenBattery Test screen Regional Settings screenUPS Display User Configuration Screens Event Log Screen AlarmSevereNormal EventLogLogInverter DC Capacitors Predictive Maintenance ScreensInverter DC Capacitors screen Inverter AC Capacitors Inverter AC Capacitors screenTop Fans Top Fans screenInverter Fans Inverter Fans screenMain Static Switch Fans Main Static Switch Fans screenPage On-line Operation Operation ModesBattery Operation Bypass Operation Manual Bypass Operation System Start-Up from Manual Bypass Operation Select Operation Configuration Select Start-upOperation Modes System Start-Up from Manual Bypass Operation System Shutdown from Online to Manual Bypass Operation Select Operation ConfigurationPage Online to Static Bypass Transfer from Online to Static Bypass OperationSelect Static Bypass Online on Operation screen Transfer from Static Bypass to Online OperationAlarm Types Alarms/TroubleshootingInfo SevereActive Alarms View active alarmsAPC Symmetra MW Remote Display Starting web-based remote session Factory Warranty WarrantyLife Support Policy Air Filter Exchange Appendix aAppendix a Air Filter Exchange Page APC Worldwide Customer Support