American Power Conversion Bypass Static manual

Page 44

Operation Modes: System Shutdown from Online to Manual Bypass Operation

System Shutdown from Online to Manual Bypass Operation of single mains/utility

systems - Step-by-Step

1.Press Operation/Configuration on the UPS Summary screen.

2.Select Shutdown on the Operation screen.

3.Press “Initiate Transfer” to initiate the transfer to Static Bypass Operation.

4.Ensure that the green H3 light is illuminated and close the Q3 maintenance bypass breaker.

5.Push OFF button on UPS display to power down the UPS.

6.Ensure that the H2 light is illuminated, indicating that it is safe to operate the Q2 breaker, and open the Q2 breaker.

7.Ensure that the green H7 and H8 lights are illuminated, and open Q7 and Q8 breakers to isolate the UPS from battery power.

8.Open the Q1 breaker.

System Shutdown from Online to Manual Bypass Operation of dual mains/utility

systems - Step-by-Step

1.Press Operation/Configuration on the UPS Summary screen.

2.Select Shutdown on the Operation screen.

3.Press “Initiate Transfer” to initiate the transfer to Static Bypass Operation.

4.Ensure that the green H3 light is illuminated and close the Q3 maintenance bypass breaker.

5.Open the Q5 static input switch breaker.

6.Push OFF button on UPS display to power down the UPS.

7.Ensure that the H2 light is illuminated, indicating that it is safe to operate the Q2 breaker, and open the Q2 breaker.

8.Ensure that the green H7 and H8 lights are illuminated, and open Q7 and Q8 breakers to isolate the UPS from battery power.

9.Open the Q1 breaker.

38

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

Image 44
Contents Symmetra MW UPS Page Contents Operation Modes Alarms/Troubleshooting Page Safety Symbols used in this guideUser Safety Display Symbols and Buttons Navigation symbolsScreen symbols UPS DisplayButtons EMOUPS Summary Screen UPS SummaryInput Summary Screens ~ ~Output Summary Screens Normal Output SummaryBypass Summary Screens ~ ~Battery Summary Screens Curve shows the batteryOperation Screen OperationUPS Start-Up Screen UPS StartupUPS Shutdown screen UPS ShutdownOnline to Static Bypass Screen Online to Static BypassStatic Bypass to Online Screen Network Settings Network Configuration ScreensNetwork Settings screen Mail Settings screen Mail SettingsSnmp Settings screen Snmp SettingsRemote Monitoring Service Settings screen Remote Monitoring Service SettingsAPC ISX Manager Settings screen APC ISX Manager SettingsUser Configuration Screens Touch-Screen Settings screenPassword Settings screen Modbus Settings screenRegional Settings screen Battery Test screenUPS Display User Configuration Screens AlarmSevereNormal EventLogLog Event Log ScreenInverter DC Capacitors Predictive Maintenance ScreensInverter DC Capacitors screen Inverter AC Capacitors screen Inverter AC CapacitorsTop Fans screen Top FansInverter Fans screen Inverter FansMain Static Switch Fans screen Main Static Switch FansPage Operation Modes On-line OperationBattery Operation Bypass Operation Manual Bypass Operation Select Operation Configuration Select Start-up System Start-Up from Manual Bypass OperationOperation Modes System Start-Up from Manual Bypass Operation Select Operation Configuration System Shutdown from Online to Manual Bypass OperationPage Transfer from Online to Static Bypass Operation Online to Static BypassTransfer from Static Bypass to Online Operation Select Static Bypass Online on Operation screenAlarms/Troubleshooting Alarm TypesInfo SevereView active alarms Active AlarmsAPC Symmetra MW Remote Display Starting web-based remote session Warranty Factory WarrantyLife Support Policy Appendix a Air Filter ExchangeAppendix a Air Filter Exchange Page APC Worldwide Customer Support