SMC Networks EX500-GEN1 Installation, Dimensions unit mm, Specifications for Input unit

Page 16

Dimensions ( unit : mm ) (continued )

When only input blocks for M12 connector are connected

DIN Rail

35

60

L3

(L4)

L2 ( Rail mounting pitch : 12.5 )

5

L1

 

44.2

(7.5)

32.2

46.9

 

Stations

1

2

3

4

5

6

7

8

L1

[mm] : Rail length

110.5

123

148

173

185.5

210.5

223

248

 

 

 

 

 

 

 

 

 

 

L2

[mm] : Mounting pitch

100

112.5

137.5

162.5

175

200

212.5

237.5

 

 

 

 

 

 

 

 

 

 

L3

[mm] : Manifold length

82

102

122

142

162

182

202

222

 

 

 

 

 

 

 

 

 

 

L4

[mm]

12

12

12.5

12.5

13

13

13.5

13.5

 

 

 

 

 

 

 

 

 

 

Installation

Connect each connector of Input unit, input blocks, and end block ( portion indicated by arrow in the figure to the right ).

Holding with hands so that there will be no gap between blocks, place the jointed unit and blocks on DIN rail.

Tighten the bolts of Input unit and end block to secure the jointed unit and blocks to DIN rail. Be sure to tighten the bolts by proper tightening torque. ( Tightening torque : 0.6Nm )

Specification

Specifications for Input unit

Item

Specification

Connected block

Current source type input block ( PNP input block )

 

or

 

Current sink type input block ( NPN input block )

 

 

Connected block station

Max. 8 blocks

 

 

Supply voltage for block

24VDC

 

 

Supply current for block

0.65A Max.

 

 

Current consumption

100mA or less ( at rated voltage )

 

 

Short circuit protection

Operates at 1A Typ. ( Cuts power supply. )

 

Can be reset by returning the power after cutting the

 

power supply to input and control section of GW unit.

 

 

Specifications for input block

Item

Specification

 

Applicable sensor

Current source type

 

Current sink type

 

( PNP output )

 

( NPN output )

 

 

 

No. of input points

2 points/8 points ( for M8 connector only )

 

 

 

Rated voltage

24VDC

 

 

 

 

Logical "1" input voltage

15V to 26.4V

 

0V to 8V

 

 

 

 

Logical "0" input voltage

0V to 5V

 

19V to 26.4V

 

 

 

 

Logical "1" input current

5mA Typ.

 

-5mA Typ.

 

 

 

 

Logical "0" input current

1.5mA

 

-1.5mA

 

 

 

Input delay time

1msec. or less

 

 

 

Indicator LED

Green LED

 

 

 

 

Insulation

N/A

 

 

 

Supply current to sensor

Max. 480mA/Input unit manifold

 

 

 

 

28

29

Image 16
Contents Reduced wiring system Contents Do not operate beyond specification range Otherwise injury or failure can resultOtherwise accident caused by malfunction can result Otherwise injury can resultSafety System configuration generalProduct Summary Manifold valve with SI unit SV/VQC seriesDimensions unit mm Installation unit mmEX500 Part Names EX500 bodySpecification Basic specificationsHigher-level bus MappingWiring SpecificationWirings is explained in the following order Lower-level busWiring Communication wiringPower supply wiring Cable connectionSingle power supplies Branch wiringCable plug For GW unit Manifold valve Input unit manifold configuration For GW unit Input unit manifold configurationSwitch setting Display/Switch SettingDisplay Display/Switch Setting Default settingsSI Unit Part Names SI unit for SV series valves EX500-SEX500-Q Mounting/WiringMounting and removing methods of SI unit are as shown below Display SI unit for SV series valve EX500-SSI unit for VQC series valve EX500-Q Applicable valve seriesWhen only input blocks for M8 connector are connected Input Unit Manifold Part NamesInstallation Dimensions unit mmWhen only input blocks for M12 connector are connected Specifications for Input unitSensor wiring Lights off Sensor signal input OFF logicalCorrespondence between input number and input block Connect sensors to the sensorEX9-OET1/EX9-OET2 EX9-PE1 EX9-PE1Part name Application Output wiring EX9-OEP1/EX9-OEP2 output connectorsDimensions when general purpose output block is connected MountingEX9-PE1 power supply connector No.0 EX9-PE1 power input connector No.1EX9-OET1 EX9-OET2 EX9-OEP1 EX9-OEP2 PWROption Troubleshooting Overall systemEtherNet/IP compatible communication COM a D LED