Installation
2.3Cable Installation
2.3.1 Wiring Preparation
! WARNING
Please read this section thoroughly before attempting to install wiring to this unit.
This UPS should be installed by a qualified / certified electrician.
Removing the Cover Plates
A branch rated overcurrent protection device (cir- cuit breaker or fused disconnect switch) must be installed for the AC input.
If the
On the back of the UPS, cover plates are over the input and output terminals, as shown at right. Keep screws and plates to one side.
Remove Cover Plates
mended that the AC input supply be protected with a circuit breaker capable of withstanding this initial inrush.
This UPS is fitted with EMI suppression filters. Earth leakage current is less than 40mA. Tran- sient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground cur- rent detection devices, as the earth leakage cur- rents of both the UPS and load will be carried.
Input and output cables must be run in separate conduits.
11