Liebert NfinityTM manual Product Warranty Registration, Specifications

Page 41

Specifications

6.0SPECIFICATIONS

General & Environmental

 

Units

 

 

Configuration

 

 

Unit Rating

 

kVA

4

 

8

 

12

 

16

 

kW

2.8

 

5.6

 

8.4

 

11.2

 

 

 

 

 

 

Compliant Safety Standards

 

 

 

 

UL 1778; c-UL

 

 

 

Conducted and Radiated EMC Levels

 

 

FCC Part 15, Class A

 

 

 

Compliant Immunity Standards

 

 

IEEE C62.41, Category B

 

 

Mechanical

 

Units

8 Bay

 

 

 

12 Bay

 

 

Width

 

20 (508)

 

 

 

20 (508)

Dimensions

 

Depth

in (mm)

28 (711)

 

 

 

28 (711)

 

 

Height

 

40 (1016)

 

 

 

54 (1372)

Environmental

 

 

Units

 

 

 

 

 

 

 

Operating Temperature (max)

F (C)

 

 

32° - 104° (0° -

40°)

 

 

Relative Humidity

 

%

 

 

0-95% non-condensing

 

 

Maximum operating altitude

 

ft. (m)

 

 

10,000 (3,000)

 

 

Nominal heat dissipation

 

BTU/Hr

1,062

 

2,124

 

3,186

 

4,248

Acoustic noise level

 

dBA

 

 

<62 @

1 meter

 

 

Input Data

 

Units

 

 

 

 

 

 

 

Nominal input voltage

 

VAC

 

 

200 or 210

 

 

 

 

 

 

 

Operating voltage range is variable based on output loading percentages

 

 

 

 

% UPS Load

 

 

 

Input Voltage

Minimum Voltage

 

 

80 – 100%

 

 

 

170 VAC

Range (Typical)

 

 

60 – 80%

 

 

 

144 VAC

 

 

 

 

30 – 60%

 

 

 

127 VAC

 

 

 

 

0 – 30%

 

 

 

110 VAC

Power factor

 

Cos Ø

 

 

>.98

 

 

 

Input frequency (nominal)

 

Hz

 

 

50 or 60

 

 

 

Input frequency range

 

Hz

 

 

40-70

 

 

 

Battery Module

 

Units

 

 

 

 

 

 

 

Number of lead acid batteries

 

 

 

10

 

 

 

Number of battery cells

 

 

 

 

60

 

 

 

Maximum charge current (full load)

A

 

 

3

 

 

 

Nominal Voltage

 

VDC

 

 

120

 

 

 

Recharge Time

 

Hrs

 

 

Typically 6 (to 90% capacity)

 

 

Output Data

 

Units

 

 

 

 

 

 

 

Output voltage

 

VAC

 

 

210/105

 

 

 

Voltage regulation

 

%

 

 

±3

 

 

 

Voltage stability (100% step load)

%

 

 

±7

 

 

 

Recovery time

 

msec

 

 

96

 

 

 

Voltage distortion

 

%

 

 

<3 THD, linear load

 

 

 

 

 

<7 THD, non-linear load

 

 

 

 

 

 

 

 

 

 

Output frequency

 

Hz

 

 

60

 

 

 

Efficiency at 100% load

 

%

 

 

89

 

 

 

 

 

 

 

 

 

110 - 125% for 10 min

 

 

Output overload capability

 

%

 

 

126-150% for 10 sec

 

 

 

 

 

 

 

 

151 - 200% for 2 cycles

 

 

6.1Product Warranty Registration

To register for warranty protection:

Visit the Quick Links section of our Web site at: http://www.liebert.com

Click on Product Warranty Registration and fill in the form. If you have any questions, please contact us at:

US: 800-222-5877

Outside the US: 614-841-6755

upstech@liebert.com

37

Image 41
Contents Nfinity Power System Page Table of Contents Figures Important Safety Instructions Glossary of Symbols General Description FeaturesSystem Description Standard ComponentsFront and back views 12 bay model shown Nfinity weight and dimensionsBackup Mode Normal ModeAuto Restart Mode Bypass ModeUnit Frame Major ComponentsUser Interface Module System Control ModuleBattery Module Power ModuleInspection Required Setup EquipmentEnvironment Site PreparationUnloading the UPS UnloadingStationary Mounting Wiring Preparation Cable InstallationGrounding Conductor Installation Input Wiring TB1Output Wiring TB3 Input Protection Connecting to External Panel BoardsLoad Rating Circuit BreakerSetup 2 210/105 VAC Setup 1 210 VAC210 VAC 210VAC and/or 105VACRepo Connection Repo switch connectionsCOM Ports CommunicationsCOM1 Relay Contacts COM2 SerialFault/Warning and Status LEDs Controls and IndicatorsDisplay Controls ButtonsNavigating the Menu Status LED ModesStart-Up and Initialization Operating ProceduresManual Transfer to Bypass Shutting Down the UPSUPS Configuration Active Alarms Service Tools UPS Status Event Log Module ReplacementMain Menu Display Date/TimeUPS Status Screen UPS Configuration Screen Review Settings Change Settings Change Configuration Settings Change Settings MenuAuto Restart Delay Auto Restart ModeInterval Start DayAlarm Mode DST ModeSet Date/Time ThresholdBypass Alarm Mode Enable Disable Display Date/Time UPS Configuration Screen Service Mode MenuService Mode Transfer to Bypass Active AlarmsEvent Log Module Replacement Clear Failures Service Tools for Liebert Global Services EngineersUser Interface Text Cause Action Active AlarmsOperation Battery Module Guide to LEDs Power ModuleModule LED Indication Control ModuleRemoving Modules Module ReplacementReplacing the User Interface Adding or Replacing ModulesScheduled Maintenance MaintenanceProper Care Replacing Fan FiltersSpecifications Product Warranty RegistrationSpecifications Page Locations Technical Support/ServiceCompany Behind the Products