Troubleshooting

4.3.2Adding or Replacing Modules

NOTE

Power Modules must be installed in the top half of the Nfinity frame. Battery Modules can be installed in any bay of the UPS frame.

1.Lift module to appropriate bay, resting end of module on bay shelf. Use caution not to rest the module on the lower bezel cover.

2.Push module into bay. Once halfway in, slide module sideways toward the center of the UPS. Continue pushing module until fully inserted.

3.Press and turn fastener clockwise until locked. If replacing a Control or Power Module, press lever down.

4.Wait about 15 seconds as the module performs a start-up test and synchronizes with the other modules. Both the yellow and green LEDs should be flashing. A green flashing LED will then confirm the module is properly installed.

5.If UPS was placed in bypass manually, transfer back to UPS operation.

6.Replace bezels.

NOTE

Turn fastener clockwise

Press lever down (for Control and Power Modules)

When replacing the Control Module, record user configuration data before removing. Re-verify the configuration settings after the new Control Module is installed.

4.3.3Replacing the User Interface

1.Lift off user interface and set it on top of the UPS frame.

2.The attached cable will be connected to an Intellislot card, found in a port between the control modules.

3.Remove the cable and the attached Intellislot card from the UPS.

4.Plug the new Intellislot card into the UPS.

5.Plug the new user interface cable into the Intellislot card.

6.Set replacement User Interface into proper position.

35

Image 39
Contents Nfinity Power System Page Table of Contents Figures Important Safety Instructions Glossary of Symbols Standard Components FeaturesGeneral Description System DescriptionFront and back views 12 bay model shown Nfinity weight and dimensionsBypass Mode Normal ModeBackup Mode Auto Restart ModeSystem Control Module Major ComponentsUnit Frame User Interface ModuleBattery Module Power ModuleSite Preparation Required Setup EquipmentInspection EnvironmentUnloading the UPS UnloadingStationary Mounting Wiring Preparation Cable InstallationInput Wiring TB1 Output Wiring TB3Grounding Conductor Installation Circuit Breaker Connecting to External Panel BoardsInput Protection Load Rating210VAC and/or 105VAC Setup 1 210 VACSetup 2 210/105 VAC 210 VACRepo Connection Repo switch connectionsCOM2 Serial CommunicationsCOM Ports COM1 Relay ContactsButtons Controls and IndicatorsFault/Warning and Status LEDs Display ControlsNavigating the Menu Status LED ModesShutting Down the UPS Operating ProceduresStart-Up and Initialization Manual Transfer to BypassDisplay Date/Time UPS Status Event Log Module ReplacementUPS Configuration Active Alarms Service Tools Main MenuUPS Status Screen UPS Configuration Screen Review Settings Change Settings Change Configuration Settings Change Settings MenuStart Day Auto Restart ModeAuto Restart Delay IntervalThreshold DST ModeAlarm Mode Set Date/TimeBypass Alarm Mode Enable Disable UPS Configuration Screen Service Mode Menu Service ModeDisplay Date/Time Active Alarms Event LogTransfer to Bypass Module Replacement Clear Failures Service Tools for Liebert Global Services EngineersUser Interface Text Cause Action Active AlarmsOperation Control Module Power ModuleBattery Module Guide to LEDs Module LED IndicationRemoving Modules Module ReplacementReplacing the User Interface Adding or Replacing ModulesReplacing Fan Filters MaintenanceScheduled Maintenance Proper CareSpecifications Product Warranty RegistrationSpecifications Page Technical Support/Service Company Behind the ProductsLocations