Installation
OUTPUT CABLING
UPS Output Terminal Block (TB3)
Connection to External Panel Boards
210 VAC
If connected equipment operates at 210VAC only, use a
Setup 1 - 210 VAC
Max output current = 76A
210 |
| L |
| 1 |
|
| |||
| L |
| 2 | |
|
|
| ||
|
|
| ||
|
|
| 3 |
|
|
|
|
| 4 | |||
Grounding Electrode Conductor GEC | ||||||||
|
|
| ||||||
(Field connection must be made) |
|
|
| |||||
|
| Connected Equipment |
|
|
| |||
|
|
|
| |||||
|
| Ground |
|
|
| |||
|
|
|
|
Panel Board Input UPS Output TB3
210 |
| L |
| 1 |
|
| |||
| L |
| 2 | |
|
| |||
|
|
| ||
|
|
| ||
|
|
| 3 | |
|
| GEC |
| 4 |
Grounding Electrode Conductor |
| |||
(Field connection must be made) |
|
|
|
G
210VAC and/or 105VAC
If connected equipment operates at 210VAC only or 105VAC only or is a combination of both, use a
Setup 2 - 210/105 VAC
Max output current = 76A
210 |
| L |
| 1 |
|
| |||
| L |
| 2 | |
|
|
| ||
|
|
| ||
|
|
| 3 |
Grounding |
|
| GEC |
|
| 4 | |
Electrode Conductor |
|
|
|
| |||
(Field connection must be made) |
|
| |||||
|
| Connected Equipment |
|
| |||
|
|
| |||||
|
| Ground |
|
| |||
|
|
|
| Panel Board Input | UPS Output TB3 | ||||
|
|
|
| L |
| 1 |
210 |
| L |
| |||
|
| 2 | ||||
|
| |||||
105 |
|
|
|
| ||
|
|
|
105
N 3
GEC 4
Grounding Electrode Conductor (Field connection must be made)
G