Operating Instructions
3.5.2UPS Configuration Screen Review Settings
Follow this procedure to review your UPS configuration settings. Follow the menus below by pressing and to review the settings.
Main Menu
UPS Status
>UPS Configuration Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools
UPS Configuration
UPS Configuration
>Review Settings Change Settings Service Mode
Review Settings
Voltage
Frequency
Battery
Alarms
Service Contact
Auto Restart
UPS Shutdown Delay
Remote Shutdown
External Battery
Bypass Alarm Mode
Air Filter Reminder
Guarantee Shutdown
Review Settings menu options
Voltage
Voltage Settings
Input 210
Output 210
Frequency
Frequency Settings Frequency Hz: 50/60 Sync Range Hz: +/- 5.0 Slew Range Hz/S: 3.0
Battery
Battery Settings Test intrvl weeks: 2 on Wed 06:00
Low Batt Warn:2 min
Alarm
Alarm Settings
Redundant Alarm:
Enabled/Disabled
Max Load: Enabled/Disabled
Service Contact
Service Contact
Liebert Corp.
www.liebert.com
Auto Restart
Auto | Restart | |
Mode: | Disable | |
Batt | % | 0% |
Delay | 10 |
UPS Shutdown Delay
UPS Shutdown Delay 120 seconds
Remote Shutdown
Remote comm shutdown Mode: Enable
External Battery
External batt config
Amp.Hr 0000 Charge (A) 00.0
Bypass Alarm Mode
Bypass Alarm Mode
Mode: Enable
Air Filter Reminder
Air Filter Reminder
Mode: 26 weeks
Guarantee Shutdown
Guarantee Shutdown Mode: Enable/Disable
22