INPUT CABLING AND PROTECTION
Table Below Applies to
UPS equipped with a Maintenance Bypass Cabinet
| Input Voltage – 200/210VAC | ||
|
|
|
|
|
|
| Recommended |
Max. System | Max. Current |
| Input Protection |
Load Rating | in UPS mode |
| Circuit Breaker |
|
|
|
|
4kVA | 18 amps |
| 50 amps |
|
|
|
|
8kVA | 36 amps |
| 50 amps |
|
|
|
|
12kVA | 53 amps |
| 75 amps |
|
|
|
|
16kVA | 70 amps |
| 100 amps |
|
|
| |
Terminal | Maximum: 35mm2 (2AWG) | ||
Block |
| Minimum: 16mm2 (6AWG) | |
Details | Torque Rating: | ||
|
|
|
|