Installation
2.3.3REPO Connection
The Nfinity is equipped with a Remote Emergency Power Off (REPO) connection.
NOTE
A jumper is factory installed between pins 1 & 2 to disable the Control Switch (SW2). This will prevent the unit from being started during installation. This jumper must be removed in order to start the unit.
Figure 2 REPO switch connections
Hanger for
REPO switch on rear of unit
REPO jumper | REPO connections | REPO connections | |||||||||
| connected |
| for normally open | for normally closed | |||||||
| as shipped | switch system | switch system | ||||||||
1 | 2 | 3 | 4 | 1 | 2 | 3 | 4 | 1 | 2 | 3 | 4 |
NOTE
Remove jumper before wiring.
If the installation does not require connection to a REPO system, the jumper must be removed.
Key to REPO switch connections
1.24 V DC, 50mA
2.Sense
3.Sense
4.Ground
! CAUTION
To maintain safety, Signal Edge Low Voltage (SELV) barriers, and electromagnetic compatibility, signal cables should be segregated and run separately from power cables.
15