Appendix D: Power Guidelines, Requirements, and Specifications
1.38A + 0.4 A + 3.1 A + 1.9 A + 3(7.6 A) =
1.38A + 0.4 A + 3.1 A + 1.9 A + 22.8 A =
29.58A @
■Input current from a DC source other than
X = 48 * 29.58 A/54 = 26.3 A
■System thermal output (based on maximally configured
Watts DC * 3.41 = BTU/hr
1,420 * 3.41 = 4,842 BTU/hr
DC Power Circuit Breaker Specifications
Each DC power supply has a single DC input
If you plan to operate a
DC Power Specifications and Requirements ■ 169