GE Energy
2.5Physical Installation
The D400 can be installed in a standard
Rack Mounting
The D400 mounts directly into an
The top cover of the D400 can get hot during peak operation. Ensure that there is at least 1U (1.75 inch [44.45 mm]) of free space above the D400 unit for proper ventilation.
When the unit is operating above the 50 °C ambient temperature, safe handling precautions are recommended to prevent burns.
»To mount the D400 on a rack:
1.Position the D400 in the rack.
2.Holding the D400 firmly in the rails of the mounting rack, insert and tighten the four rack screws.
The recommended tool torque settings for
–
–
–M5x0.45 screws use 18.1
–M6x0.5 screws use 33.3
Panel Mount
»To mount the D400 in a panel:
If you are using a panel cutout, use the following cutout dimensions:
| .162 in. |
[4.1 mm] | |
3.50 in. [88.90 mm] | 1.75 in. [44.46 mm] |
18.3 in. [464.8 mm]
17.5 in. [444.5 mm]
Cutout for panel mounting
D400 Substation Data Manager User's Manual 23