GE Energy
5.2Power Connections
The D400 accepts power connections through two terminal blocks on the rear panel:
•Terminal block TB1 is reserved for connecting power from one or two external sources to the D400.
•Terminal block TB2 provides contact closure outputs for power supply fail and system fail alarms.
Protective Earth
Terminal
Power Supply
Connections
Power Supply
Alarms
Wiring Requirements
The supply wiring for the D400 must be a minimum of 18 AWG (0.79 mm²),
The protective conductor must be minimum 16 AWG (1.3 mm²) wire with
The wires must be terminated with an insulated #6 Forked Terminal.
The clear plastic protective barrier provided with the terminal strip connector must be in place once wiring of the mains is completed.
D400 Substation Data Manager User's Manual 65