GE Energy
IRIG-B Input Adapter
Switch SW2 Configuration
Switch SW2 controls the signal option for the selected state option (SW1). It contains three switch positions that can be set to ON or OFF to select the appropriate signal.
Input Signal Option |
| SW2 Switch Positions | ||
|
|
|
| |
1 |
| 2 | 3 | |
|
| |||
|
|
|
|
|
Fiber Optic (RX) | ON |
| OFF | OFF |
|
|
|
|
|
TTL (TB1) (default) | OFF |
| ON | OFF |
|
|
|
|
|
BNC (J2) | OFF |
| OFF | ON |
|
|
|
|
|
Switch SW3 Configuration
Switch SW3 controls the state option for the
Fiber Optic TX Option | SW3 Switch Positions | ||
|
| ||
1 | 2 | ||
| |||
|
|
| |
Fiber RX (default) | ON | OFF | |
|
|
| |
Inverted | OFF | ON | |
|
|
|
D400 Substation Data Manager User's Manual 37