Force10 Networks manual Cable Connector Required for E1200i DC PEM

Page 45

Step

Task (continued)

5.Secure the chassis ground connection first:

a Remove one outer nut and one washer from each of the six studs. One nut should remain, tight on the stud. If the inner nut is loose, re-tighten it to 25 inch/lbs. maximum.

b Locate the chassis ground connector studs on the PEM front panel (see Figure 16). The two rightmost studs are the ground connection.

c Install the grounding cable onto the ground studs. The grounding cable must comply with your local electrical codes in size and color (typically the color is green or green with yellow stripe).

NOTE: Grounding cables must be terminated only with a UL-listed 2-hole lug with 1/4-inch holes on 3/ 4-inch spacing (see Figure 17).

d Replace the two washers and nuts on the studs.

e With a 7/16-inch box or socket wrench, tighten the nuts (torque should not exceed 25inch/lbs).

f Connect the opposite end of the grounding cable to the nearest appropriate facility grounding post.

Figure 17 Cable Connector Required for E1200i DC PEM

All meas urements s hown in inches .

High-s trand-count conductor

0.267 diameter 2 Holes

fn00105lp

0.750"

6.Connect the -48 VDC and Return cables from each PEM to the remote power sources (circuit breakers A and B).

a Check that the remote power sources (for example, circuit breakers) are in the OFF position. b Locate the appropriate studs on the PEM front panel (Figure 16).

c The two leftmost studs on the PEM are the -48 VDC (-) connection. The cable attached to these studs is typically black.

The two middle studs are the return (+) connection. The cable attached to these studs is typically red.

dInstall the -48 VDC and Return cables on the studs. The cables should be of the size and color to comply with local electrical codes.

Note: Power cables must be terminated only with a UL-listed 2-hole lug with 1/4-inch studs with 3/4-inch spacing (Figure 19).

eReplace the washers and nuts on the studs.

fWith a 7/16-inch box or socket wrench, tighten the nuts.

Installing and Maintaining the E1200i System

45

Image 45
Contents Installing and Maintaining the E1200i System Copyright 2008 Force10 Networks Contents Installing Fan Trays Appendix B System Boot Index List of Figures Page List of Tables Page Symbol Description Defines the information symbols used throughout this guideRelated Publications Operating Overview E1200i SystemPage Page RPM Component Minimum Maximum Field-Replaceable Step Task Section Supplying Power DC onSite Selection Criteria Chapter Site PreparationCabinet Placement PowerRack Mounting Fans and Airflow Storing Components Unpacking the E1200i AC System Installing the AC ChassisTo install a equipment rack shelf bar Installing the Equipment Rack Shelf BarStandard Front Chassis Mounting Step TaskTo install the chassis into a prepared rack Installing the Chassis into an Equipment CabinetInstalling the AC Chassis Unpacking the E1200i DC System Installing the DC ChassisInstalling the DC Chassis Rack-Mounting the Chassis Installing the DC Chassis Installing Fan Trays Screw latch Installing Fan Trays Is an illustration of the fan tray safety labels To install fan traysLabel LocationInstalling Fan Trays On/Standby Switch Installing AC Power SuppliesSecuring the Chassis Ground Installing Power SuppliesInsert power supply AC Power Supply and Fan Operability TestStatus LED is Step TaskStatus Installing AC Power Supplies PEM 0 and PEM 1 Chassis Locations Installing DC Power SuppliesInstalling DC PEMs Cable and Connector RequirementsUse the following steps to install a DC PEM Over current protector PEM interlock lever Locking screws Cable Connector Required for E1200i DC PEM DC PEM with Connections in Place DC Power Supply and Fan Operability Test Step Task Installing RPMs, Line Cards SFMs Unpacking an RPM or Line CardImportant Points to Remember Installing Line Cards and RPMs RPMsLine Cards Blank Panels Preparing and Installing RPMs and Line CardsInstalling an RPM into the E1200i To install line cards and RPMsRPM Label and LEDs Installing a Second RPMDescribes the RPM LED states and the RPM front panel Section Label DescriptionInstalling Switch Fabric Modules SFMs Illustrates the SFM front panel and LEDs SFM Front Panel and LEDsLine Card Cable Management Systems Connecting the Console and Auxiliary Ports RPM Ports and CablesRPM Ports Cable and Adapter Pin Assignments Pin Signal Input/OutputAccessing the Console with a DB-25 Adapter Accessing the Console with a DB-9 AdapterAccessing the 10/100 Ethernet Management Port Accessing the Auxiliary Port by ModemLabel Description Preparation Chapter Powering UpSupplying Power DC Supplying Power ACBooting from the Bootuser Prompt Booting to the CLI PromptPowering Up Removing and Replacing Fan Trays Removing and Replacing ComponentsRemoving and Replacing Components Removing and Replacing AC Power SuppliesInstalling and Maintaining the E1200i System Removing and Replacing DC Power Supplies Remove an AC Power Supply in a non-redundant installationRemove an AC Power Supply in a redundant installation Installing and Maintaining the E1200i System Remove a DC Power Supply Removing and Replacing RPMs, Line Cards, or SFMs Removing and Replacing line cards or RPMsTo remove and replace E1200i line card or RPM modules Removing and Replacing SFMs To remove and replace an SFMNo linecard To remove and replace the air filter Removing and Replacing the Air FilterRemoving and Replacing Components Appendix a Using a Flash Memory Card External Flash Memory Card OverviewInserting the External Flash Memory Card Removing the External Flash Memory Card To install the flash memory cardFormatting an External Flash Card To remove the flash memory cardCommand Syntax Command Mode Purpose Copying Files to the External FlashDisplaying Files Stored on the External Flash Page Booting from the Bootuser Prompt System Boot ProcessStep Command To configure the chassis from the Bootuser promptStep Command Task Show boot selectorShow bootvar View the Management interface’s physical settings Auto-negotiationPort Show default-gateway Default-gateway ip-address Step CommandTaskReload System Boot Appendix C Alarms Power Supplies and Alarms SFMs and Alarms Alarms E1200i AC System Power Requirements Appendix D System SpecificationsE1200i AC Chassis Physical Design This appendix contains two major sectionsSystem Specifications E1200i DC Chassis Physical Design E1200i DC System Power RequirementsOperating Specifications Environmental SpecificationsAgency Compliance Non-operatingSafety Standards and Compliance Agency Certifications Japan Vcci Compliance for Class a EquipmentKorea MIC certification Electromagnetic Emissions ImmunityProduct Recycling and Disposal European Weee symbol System Specifications This appendix contains these major sections Appendix E Technical SupportSupport Policies section of iSupport Accessing iSupport ServicesOutput from the show logging eventlog unit command, where Output from the show tech-supportnon-paged command ThisConsole captures showing the error messages Console captures showing the troubleshooting steps takenTo request replacement hardware, follow these steps Requesting a Hardware ReplacementFPC Asic Index104 Index Installing and Maintaining the E1200i System 105