Eaton Electrical BladeUPS Bar manual Wireway Installation

Page 12

INSTALLATION

Rear of Rack

Side Bracket Adjustment Screws

(3 places each side)

Adjustable Side Brackets (1 each side)

4.Install an M6 hex nut onto each of the three wireway studs to secure the wireway to the rear of the rack. Install the first stud in the fourth hole location from the bottom. Do not tighten the nuts. Figure 4 shows the nuts installed.

5.Loosen the three adjustment screws on each side of the wireway housing and adjust the side brackets for the depth of the rack. Do not retighten the screws.

6.Install six M6×12 pan-head screws and M6 split lock washers to secure the two wireway side brackets to the front of the rack. Install the first screws in the fifth hole location from the bottom. Torque the screws to 5.1 ± 0.8 Nm (45 ± 7 lb in).

7.Tighten the three M6 hex nuts installed in Step 4. Torque the nuts to 5.1 ± 0.8 Nm (45 ± 7 lb in).

8.Retighten the six side bracket adjustment screws loosened in Step 5. Torque to 3.4 Nm (30 lb in).

M6 Hex Nuts on Wireway Studs

(3 places)

Wireway

Housing

M6×12 Pan-Head Screws and M6 Split Lock Washers

(3 places each side)

Front of Rack

Figure 3. Wireway Installation

8

EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01

Image 12
Contents Powerware BladeUPS Bar Installation Guide Special Symbols Table of Contents Table of Contents Chapter Introduction Consignes DE Sécurité Importantes Conserver CES Instructions Wichtige Sicherheitsanweisungen Aufbewaren Viktiga Säkerhetsföreskrifter Spara Dessa Föreskrifter Chapter Installation Checking the Package Contents U T I O N Wireway Installation Ferrite and Bar Placement Bar Base Installation Bar Bracket Installation Wireway Tab Attachment Wireway Terminal Block Housing Installation Wireway Access Cover Installation Front Cover Mounting Panel Installation Snap the two front covers into place, as shown in Figure Chapter Specifications Specifications Service and Support Service and Support Page Page Page 164201723P01