Eaton Electrical BladeUPS Bar manual Wireway Terminal Block Housing Installation

Page 17

INSTALLATION

17.Using two M6×12 hex bolts, secure the left side of the wireway terminal block housing to the rack. See Figure 8. Torque the bolts to 5.1 ± 0.8 Nm (45 ± 7 lb in).

18.Using nine M4×8 pan-head screws, secure the wireway terminal block housing to the wireway and to the bar. See Figure 8. Torque the screws to 1.7 ± 0.2 Nm (15 ± 2 lb in).

Wireway

Terminal Block

Housing

M6×12 Hex Bolts (2 places)

M4×8 Pan-Head Screws (9 places)

Figure 8. Wireway Terminal Block Housing Installation

EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01

13

Image 17
Contents Powerware BladeUPS Bar Installation Guide Special Symbols Table of Contents Table of Contents Chapter Introduction Consignes DE Sécurité Importantes Conserver CES Instructions Wichtige Sicherheitsanweisungen Aufbewaren Viktiga Säkerhetsföreskrifter Spara Dessa Föreskrifter Chapter Installation Checking the Package Contents U T I O N Wireway Installation Ferrite and Bar Placement Bar Base Installation Bar Bracket Installation Wireway Tab Attachment Wireway Terminal Block Housing Installation Wireway Access Cover Installation Front Cover Mounting Panel Installation Snap the two front covers into place, as shown in Figure Chapter Specifications Specifications Service and Support Service and Support Page Page Page 164201723P01