Eaton Electrical BladeUPS Bar manual Ferrite and Bar Placement

Page 13

INSTALLATION

9.Place the ferrite assembly on the floor of the wireway and secure with the supplied tie wrap. Loop the tie wrap through both attachment sites on the wireway floor and through the ferrite assembly. See Figure 4.

10.Note the orientation of the base bracket installed on the bar for later re-installation (see Figure 5). Remove and retain the base bracket and hardware.

11.Place the bar in the rack as shown in Figure 4.

NOTE The bar can rest on the floor of the rack until secured in place. After complete installation, the bar will be secured to the rack and wireway as shown in Figure 4.

M6 Hex Nuts on Wireway Studs

(3 places)

Ferrite Assembly (secured to wireway floor with tie wrap)

Rear of Rack

Figure 4. Ferrite and Bar Placement

Bar

Wireway Floor Tab

(above bar base sheetmetal)

EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01

9

Image 13
Contents Powerware BladeUPS Bar Installation Guide Special Symbols Table of Contents Table of Contents Chapter Introduction Consignes DE Sécurité Importantes Conserver CES Instructions Wichtige Sicherheitsanweisungen Aufbewaren Viktiga Säkerhetsföreskrifter Spara Dessa Föreskrifter Chapter Installation Checking the Package Contents U T I O N Wireway Installation Ferrite and Bar Placement Bar Base Installation Bar Bracket Installation Wireway Tab Attachment Wireway Terminal Block Housing Installation Wireway Access Cover Installation Front Cover Mounting Panel Installation Snap the two front covers into place, as shown in Figure Chapter Specifications Specifications Service and Support Service and Support Page Page Page 164201723P01