Cyclades PM IPDU manual Cyclades PM20i-32A Ipdu, Cyclades PM20i-32Au Ipdu

Page 23

Chapter 1: Introduction

11

 

 

Vertical mounting (zero U)

Figure 1.10: The Cyclades PM20i IPDU, PM20i-32A IPDU and PM20i-32AU IPDU

Cyclades PM20i-32A IPDU

The Cyclades PM20i-32A IPDU has the following features:

32A input power cord; IEC 309 plug.

Twenty 240VAC/10A power receptacles (IEC320-C13)

240VAC/two 16A magnetic circuit breakers with accidental-off protection function

Vertical mounting (zero U)

Refer to Figure 1.10 on page 11 for an image of the Cyclades PM20i-32A IPDU.

Cyclades PM20i-32Au IPDU

The Cyclades PM20i-32Au IPDU has the following features:

32A unterminated input power cord

Twenty 240VAC/10A power receptacles (IEC320-C13)

240VAC/two 16A magnetic circuit breakers with accidental-off protection function

Vertical mounting (zero U)

Refer to Figure 1.10 on page 11 for an image of the Cyclades PM20i-32Au IPDU.

Image 23
Contents Cyclades P M Ipdu FCC Warning Statement Canadian DOC Notice Cyclades PM Ipdu Power On Table of Contents Configuration Appendices Vi Cyclades PM Ipdu Installer/Administrator/User Guide List of Figures Viii Cyclades PM Ipdu Installer/Administrator/User Guide List of Tables Cyclades PM Ipdu Installer/Administrator/User Guide Sequential power up Features and BenefitsAlarms and monitoring Creation of user accounts Hardware Configuration OptionsStandalone configuration Support for daisy chainingStandalone Configuration Daisy chained configurationUser Integrated configurationPM Ipdu #2 PM Ipdu #3 PM Ipdu #4 An integrated environment offers the following advantagesTo connect a Cyclades PM Ipdu to an Avocent DSR switch Accessing the System ConsoleDirect console access Console access through a management deviceCyclades PM8 Ipdu Component OverviewCyclades PM10 Ipdu Cyclades PM8i IpduCyclades PM10i-32A Ipdu Cyclades PM10i IpduCyclades PM10i-L30A Ipdu Cyclades PM20i Ipdu Cyclades PM10i-32Au IpduCyclades PM20 Ipdu Cyclades PM20i-32Au Ipdu Cyclades PM20i-32A IpduCyclades PM Ipdu Installer/Administrator/User Guide Supplied with the PM Ipdu Getting StartedConnector on Modular input power cables for the PM IpduPM8i-10A Ipdu and PM10i-10A Ipdu power cables Rack Mounting the Cyclades PM Ipdu PM10i-15A Ipdu power cablesPM10i-16A Ipdu and PM 20i-16A Ipdu power cables PM10i-20A Ipdu and PM 20i-20A Ipdu power cablesRack Mounting a Cyclades PM10 IPDU, PM10l Ipdu and PM8iIPDU Installation environmentLocate the appropriate sets of holes on the PM Ipdu To mount the Cyclades PM8i IPDU, PM10 Ipdu or PM10i IpduTo daisy chain a PM Ipdu Daisy Chaining PM IPDUsPlugging Devices Into PM Ipdu Outlets Powering Up the PM IpduMaking a Direct Connection for Console Access To power up the PM IpduConnecting a Local Work Station to the Cyclades PM Ipdu To access the consoleTo log into the PM Ipdu through the console in port Default Configuration Parameters ConfigurationTo assign outlets to users with the assign command Initial Configuration Using the Command PromptTo change the default password To create users with the adduser commandTo reset the admin password using the loopback connector Resetting the Admin PasswordTo save the configuration with the save command Upgrading the Cyclades PM Ipdu Firmware To upgrade PM Ipdu firmwareTo use HyperTerminal in Windows PmupgradeTo use Minicom in Linux Sending Firmware using HyperTerminalSending Firmware using Minicom Cyclades PM Ipdu Installer/Administrator/User Guide Number of PM Ipdu outlets Daisy chained PM IPDUs in the login promptPM Ipdu User Interface Number of PM IPDUsLogging in to the PM Ipdu CommandsExamples AdduserSyntax ArgumentsTo read the threshold, enter the following AlarmAssign To set the threshold, enter the followingTo turn buzzer notification on or off, enter the following BuzzerCurrent Pm current To reset maximum current drawn, enter the followingPmcurrent reset CurrentprotectionTo view the current load of segment A, enter the following CurrsegExample To cycle one outlet, enter the following CycleTo view the current load of segment B, enter the following None DbsyncDeluser To cycle multiple outlets, enter the followingPmdisplay 2 DisplayTo delete the user rog, enter the following Pmdeluser rogTo view the display status, enter the following FactorydefaultsExit command exits the session ExitPmsyslog help To reset the factory defaults, enter the followingPmfactorydefaults HelpPmhelp HumidityPm humidity Pmhumidity resetHwocp Pmid 1 R&D Pmhwocp 1 resetTo set the ID of PM Ipdu 1 R&D, enter the following PmhwocpPmid IntervalTo display the ID of PM Ipdu 2, enter the following To display the interval of outlet 1, enter the followingPmlist ListPminterval 2,4-6 To name outlet 4 as nowhere, enter the following LockName To lock outlets 1, 2, and 6, enter the followingPmoff OffTo turn all outlets off, enter the following Pmoff allPmon 1 PasswdTo turn on outlets 1, 3, 4, and 5, type Pmpasswd RebootPmpasswd alpha Pmreboot Arguments Examples RestorePmrestore SaveTo display the status of outlet 1, enter the following To save the configuration to flash, enter the followingStatus command displays the status of selected outlets StatusPmsyslog SyslogTo display the status of all outlets, enter the following Pmstatus allPmsyslog on TemperaturePm temperature Pmtemperature resetPmunassign 2,4 diderot UnassignUnlock To unlock outlets 2, 3, 4, and 8, enter the followingUpgrade Ver To upgrade 1, typePmver VoltagePmwhoami WhoamiTo view the current username, enter the following Cyclades PM Ipdu Installer/Administrator/User Guide Appendix a Specifications Cyclades PM Ipdu Installer/Administrator/User Guide Appendices Cyclades PM Ipdu Installer/Administrator/User Guide Appendices Table A.11 PM10i-32A Ipdu and PM10i-32Au Ipdu Specifications Table A.13 PM20-20A Ipdu and PM20-L20A Ipdu Specifications Cyclades PM Ipdu Installer/Administrator/User Guide Appendices Interface Pinouts Safety Instructions Appendix B Safety InstructionsSicherheitsanweisungen Istruzioni di Sicurezza Instruções de Segurança Instrucciones de seguridad Instructions de sécurités PM8i Ipdu and PM10i Ipdu Appendix C Circuit BreakersPM Ipdu Units with One Circuit Breaker PM10i-32A Ipdu and PM10i-32Au Ipdu PM10i-L30A IpduPM20i-L30A Ipdu PM20-L30A IpduPM20i-32A Ipdu and PM20i-32Au Ipdu Circuit Breaker Trip Time Cyclades PM Ipdu Installer/Administrator/User Guide Index Cyclades PM Installer/Administrator/User Guide Index Cyclades PM Installer/Administrator/User Guide Page 590-667-501A