Chapter 4: Command Line Interface | 37 |
|
|
Examples
To display current protection status for all units, enter the following.
pm>currentprotection status
IPDU #1: Overcurrent protection is OFF.
IPDU #2: Overcurrent protection is OFF.
To enable current protection status for all units, enter the following.
pm>currentprotection ON
IPDU #1: Overcurrent protection turned ON.
IPDU #2: Overcurrent protection turned ON.
To disable current protection status for all units, enter the following.
pm>currentprotection off
IPDU #1: Overcurrent protection turned OFF.
IPDU #2: Overcurrent protection turned OFF.
currseg
The currseg command lets you view the current for the lower or upper segment of outlets. This command is only useful for IPDUs with dual current sensors (30A and 32A models). The lower segment (segment A) would be outlets
Syntax
currseg AB [reset]
Arguments
AB segment A or segment B
reset Clears the max recorded current for A & B.
Example
To view the current load of segment A, enter the following.
pm>currseg A
IPDU #1: True RMS current for segment A: 0.4A. Maximum current for
segment A: 0.
4A