National Instruments network module quick start FP-1600 Specifications, 11 to 30 VDC

Page 17

FP-1600 Specifications

Network interface

10BaseT and 100BaseTX Ethernet

Compatibility

IEEE 802.3

Communications rate

10 Mbps, 100 Mbps, autonegotiated

Cabling distance

100 m

Power supply range

11 to 30 VDC

Power consumption

7 W + 1.15 * (I/O module power requirements)

Maximum terminal bases per bank

9

Maximum number of banks

determined by network topology

Operating temperature

–20 to +55 °C

Storage temperature

–55 to +85 °C

Relative humidity

5% to 90% non-condensing

Weight

280 g (9.9 oz.)

Compliance

Electrical safety . . . . . . . . . . . . . . . . . . . . . . designed to meet IEC 1010 EMI emissions/immunity . . . . . . . . . . . . . . . CISPR 11

CE Mark Compliance

This product meets applicable EU directive(s) as follows: EMC directive

Immunity . . . . . . . . . . . . . . . . . . . . . . EN 50082–1:1994

Emissions . . . . . . . . . . . . . . . . . . . . . EN 55011:1991 Group I Class A at 10 meters

17

Image 17
Contents Install the Network Module What You Need to Get Set UpLock rail clip Install the Terminal Bases Place protective cover on last base Connect the Network Cables Install the I/O ModulesWire Power to Your FieldPoint System FP-1600 FP-AI-100 FP-AO-200 FP-AI-110 Connect to Field DevicesPower Up Your FieldPoint System Verify the Installation Install the FieldPoint SoftwareEthernet as the Type Click on Find Devices IP address is the address of the FP-1600 on the networkSelect File»Save Configure I/O Modules Select File»Save when you are done Where to Go from Here 11 to 30 VDC FP-1600 SpecificationsMechanical Dimensions Copyright 1999, 2000 National Instruments Corporation