Page 23 of 36 |
4.1.29.System Control Commands containing no Parameters: Timeclock new schedule
//Client side Map Descriptors
Map_Descriptors |
|
|
|
|
|
|
|
|
Map_Descriptor_Name, Data_Array_Name, | Data_Array_Offset, | Function, | Node_Name, | GRAFIK_command, | DA_Lut_List, | DA_Lut_List_Offset, | Length | |
Tck_new_sched, | Lut_triggers, | 12, | awt, | LUT_GRF6_0, | tclk_new_schedule, | Clk_sched, | 0, | 1 |
DA_Lut_List data setup |
|
Position from DA_Lut_List_Offset | Description |
0 | Area tclk 0 |
1 | Schedule 0 |
2 | Area tclk 1 |
3 | Schedule 1 |
.. | .. |
60 | Area tclk 30 |
61 | Schedule 30 |
62 | Area tclk 31 |
63 | Schedule 31 |
Note: 1 to 32 new schedules may be started by this command. To trigger this command, write the number of area timeclocks into the Data Array specified by Data_Array_Name at Data_Array_Offset.
4.1.30.System Control Commands containing no Parameters: Set timeclock
// Client side Map Descriptors Map_Descriptors
Map_Descriptor_Name, | Data_Array_Name, | Data_Array_Offset, | Function, | Node_Name, | GRAFIK_command, | DA_Lut_List, | DA_Lut_List_Offset, | Length |
Set_tck, | Lut_triggers, | 13, | awt, | LUT_GRF6_0, | set_tclk, | Set_tclk, | 0, | 1 |
DA_Lut_List data setup |
|
|
|
|
|
|
| |
Position from DA_Lut_List_Offset | Description |
|
|
|
|
|
| |
0 |
| Hour ( |
|
|
|
|
|
|
1 |
| Minutes ( |
|
|
|
|
| |
2 |
| Month ( |
|
|
|
|
| |
3 |
| Day of month ( |
|
|
|
|
| |
4 |
| Year ( 0 – 99 ) |
|
|
|
|
| |
5 |
| Day of week ( |
|
|
|
|
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408)