FieldServer FS-8700-84 System Control Commands containing no Parameters Halt Zone

Page 20

FS-8700-84_Lutron_eLumen Driver Manual

Page 17 of 36

4.1.17.System Control Commands containing no Parameters: – Halt Zone

//Client side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name, Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Zone_halt,

Lut_triggers,

0,

awt,

LUT_GRF6_0,

halt_zone,

Zone_list,

0,

1

DA_Lut_List data setup

 

Position from DA_Lut_List_Offset

Description

0-63

Zone(s) to halt

Note: After setting up the zone numbers to halt in the DA_Lut_List Data Array, trigger this command by writing the number of zones to halt into the Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.

4.1.18.System Control Commands containing no Parameters: – Stop Scene Ramp Up

// Client side Map Descriptors Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Stop_scn_rmp_up,

Lut_triggers,

1,

awt,

LUT_GRF6_0,

stop_scene_ramp_up,

Area_list,

0,

1

DA_Lut_List data setup

 

 

 

 

 

 

 

Position from DA_Lut_List_Offset

Description

 

 

 

 

 

 

0-31

 

Area(s) with scenes to stop ramp up

 

 

 

 

Note: After setting up the area numbers to stop scene ramps in the DA_Lut_List Data Array, trigger this command by writing the number of areas into the Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 20
Contents FS-8700-84 Lutron eLumen Effective for all systems manufactured after May 1Table of Contents Appendix a Appendix BLutron eLumen Description Required 3rd Party Hardware Driver Scope of SupplyFieldServer Technologies Description Hardware Connections FS-B2010Lutron Elumen RS-485 Example Section TitleColumn Title Function Legal Values None Link, Area, Linkstation, Switch, Zone, Sysvar, Panel DAAreaNames, DASceneNames, DAZoneNames, xxxOffsetDALutList, DALutListOffset DALutParms, DALutParmsOffsetARS, RDBC, Wrbc Column Title Function Legal Values Column Title Function Timing Parameters Column Title Function Legal ValuesSystem Monitor Command Time Now System Monitor Command Astro TimesSystem Monitor Command Bootcode Revision Level System Monitor Command DateSystem Monitor Command Code Revision Level System Monitor Command Serial Number System Monitor Command Area StatusSystem Monitor Command Timeclock Status System Monitor Command Zone IntensitySystem Monitor Command Request Panel Emergency Status System Monitor Command System Variable ValueSystem Monitor Command Wallstation Status System Monitor Command Switch StatusSystem Control Commands containing no Parameters Halt Zone Client side Map Descriptors MapDescriptorsArea timeclocks to disable Area timeclocks to re-enable System Control Commands containing no Parameters Run scripts Zone Intensity Fade Delay Zone number Area Scene Area tclk Enawallstation Ctrlwslist Link number Areas with scenes to stop ramp down System Control Commands Containing Parameters Toggle zone System Control Commands Containing Parameters Ramp zones up Zones to pommel or pulse Zones to flash System scene numbers System variable numbers NodeName GRAFIKcommand Link Rawswsts00 Passive Active read on startup Retrieving names Getnames AreaNames 511FS-8700-84LutroneLumen Driver ManualPage 35 Appendix B. Revision History Date Resp Format Driver Comment Ver Rev